Lenovo XClarity Energy Manager offers the following capabilities:
Monitors room, row, rack, and device levels in the data center
Reports vital system information, such as power, temperature and resource utilization
Monitors inlet temperature to locate hot spots, reducing the risk of data or device damage
Provides finely-grained controls to limit platform power in compliance with IT policy
Generates alerts when a user-defined threshold is reached
Lenovo XClarity Energy Manager license is included in the XClarity Controller Enterprise upgrade.
Physical specifications
The ThinkAgile HX2320-E appliances have the following dimensions and weight (approximate):
Height: 43 mm (1.7 in.)
Width: 434 mm (17.1 in.)
Depth: 715 mm (28.1 in.)
Weight (maximum): 18.8 kg (41.4 lb)
The ThinkAgile HX2720-E appliances have the following dimensions and weight (approximate):
Enclosure
Height: 87 mm (3.4 in.)
Width: 448 mm (17.6 in.)
Depth: 834 mm (32.8 in.)
Weight (maximum, with four nodes): 55.0 kg (121.3 lb)
Node
Height: 41 mm (1.6 in.)
Width: 222 mm (8.7 in.)
Depth: 562 mm (22.1 in.)
Weight (maximum): 7.5 kg (16.5 lb)
Operating environment
The HX Series appliances comply with ASHRAE class A2 specifications. The HX2320-E and HX2720-E
appliances also complies with ASHRAE class A3 and class A4 specifications. The appliance performance
might be impacted when the operating temperature is outside the ASHRAE A2 specifications.
The HX Series appliances are supported in the following environment:
Air temperature:
Operating:
ASHRAE Class A4: 5 °C - 45 °C (41 °F - 113 °F); for altitudes above 900 m (2,953 ft),
decrease the maximum ambient temperature by 1 °C for every 125-m (410-ft) increase
in altitude
ASHRAE Class A3: 5 °C - 40 °C (41 °F - 104 °F); for altitudes above 900 m (2,953 ft),
decrease the maximum ambient temperature by 1 °C for every 175-m (574-ft) increase
in altitude
ASHRAE Class A2: 10 °C - 35 °C (50 °F - 95 °F); for altitudes above 900 m (2,953 ft),
decrease the maximum ambient temperature by 1 °C for every 300-m (984-ft) increase
in altitude
Non-operating: 5 °C - 45 °C (41 °F - 113 °F)
Storage: -40 °C - +60 °C (-40 °F - 140 °F)
Maximum altitude: 3,050 m (10,000 ft)
Lenovo ThinkAgile HX2320-E and HX2720-E Appliances
22