Operating environment
The ThinkAgile VX3320 appliances comply with ASHRAE class A2 specifications. The appliance performance
might be impacted when the operating temperature is outside the ASHRAE A2 specifications. Depending on the
hardware configuration, some VX3320 appliances comply with ASHRAE class A3 and class A4 specifications.
To comply with ASHRAE class A3 and class A4 specifications, the appliance must meet the following hardware
configuration requirements at the same time:
Two power supplies installed.
No NVMe PCIe SSDs installed.
Processors with TDP more than or equal to 150 W not installed.
Intel Xeon 4112, 5122, 6126, 6128, 6132, 6134, 6134M, and 8156 processors not installed.
The ThinkAgile VX3320 appliances are supported in the following environment:
Air temperature:
Operating:
ASHRAE Class A4: 5 °C - 45 °C (41 °F - 113 °F); for altitudes above 900 m (2,953 ft),
decrease the maximum ambient temperature by 1 °C for every 125-m (410-ft) increase in
altitude
ASHRAE Class A3: 5 °C - 40 °C (41 °F - 104 °F); for altitudes above 900 m (2,953 ft),
decrease the maximum ambient temperature by 1 °C for every 175-m (574-ft) increase in
altitude
ASHRAE Class A2: 10 °C - 35 °C (50 °F - 95 °F); for altitudes above 900 m (2,953 ft),
decrease the maximum ambient temperature by 1 °C for every 300-m (984-ft) increase in
altitude
Non-operating: 5 °C - 45 °C (41 °F - 113 °F)
Storage: -40 °C - +60 °C (-40 °F - 140 °F)
Maximum altitude: 3,050 m (10,000 ft)
Humidity:
Operating:
ASHRAE Class A4: 8% - 90% (non-condensing); maximum dew point: 24 °C (75 °F)
ASHRAE Class A3: 8% - 85% (non-condensing); maximum dew point: 24 °C (75 °F)
ASHRAE Class A2: 8% - 80% (non-condensing); maximum dew point: 21 °C (70 °F)
Storage: 8% - 90% (non-condensing)
Electrical:
100 - 127 (nominal) V AC; 50 Hz / 60 Hz (750 W Platinum and 1100 W power supplies only)
200 - 240 (nominal) V AC; 50 Hz / 60 Hz
180 - 300 V DC (supported in China only)
Acoustics (maximum configuration, operating): 6.0 bels
Vibration:
Operating: 0.21 G rms at 5 Hz to 500 Hz for 15 minutes across 3 axes
Non-operating: 1.04 G rms at 2 Hz to 200 Hz for 15 minutes across 6 surfaces
Shock:
Operating: 15 G for 3 milliseconds in each direction (positive and negative X, Y, and Z axes)
Non-operating:
12 kg - 22 kg: 50 G for 152 in./sec velocity change across 6 surfaces
23 kg - 31 kg: 35 G for 152 in./sec velocity change across 6 surfaces
Lenovo ThinkAgile VX3320 Appliance (Xeon SP Gen 1) (withdrawn product)