Armstrong HEM-93M Installation And Operation Manual - Page 6

Browse online or download pdf Installation And Operation Manual for Humidifier Armstrong HEM-93M. Armstrong HEM-93M 18 pages. Humidifiers for air handling systems

Methods of Installing Humidifiers
The standard method of installing Armstrong humidifiers is
with the humidifier body vertical (do NOT mount body
horizontally) and the manifold discharging into the air flow.
For operator orientation see manufacturer's data. Pipe and
May be used with 91 - 94 Cast Iron, and 1200 - 1400 Stainless Steel Humidifiers
Figure 4-1. Horizontal Installation
Strainer
Trap
Figure 4-2. Installation Method Where Obstructions Prevent Direct Manifold Connection
Strainer
Trap
Note: Maximum distance recommended from humidifier to manifold is 5-10 feet.
4
Primary Methods of Installation
N Min.
Drip Leg
Dirt Pocket
N Min.
Drip Leg
Dirt Pocket
fittings indicated by dotted lines are furnished by installing
contractor. Dimensions and pipe sizes are given in
Tables 8-1 and 8-2 on Page 8.
Manifold
Insulate (Avoid Use of
Elbows or Extra Fittings)
Pipe Adaptor
Manifold
OR
U Min.
OR
U Min.