Armstrong FLO-RITE-TEMP 665 Installation And Adjustment Instructions - Page 2

Browse online or download pdf Installation And Adjustment Instructions for Water Heater Armstrong FLO-RITE-TEMP 665. Armstrong FLO-RITE-TEMP 665 17 pages. Instantaneous water heater. instructions for single and double wall units
Also for Armstrong FLO-RITE-TEMP 665: Installation And Adjustment Instructions (20 pages)

Armstrong FLO-RITE-TEMP 665 Installation And Adjustment Instructions

INSTALLATION AND ADJUSTMENT INSTRUCTIONS

No water heater will work satisfactorily if improperly installed and operated. These instructions contain
important information for the installation and adjustment of the FLO-RITE-TEMP Water Heaters. Read
these instructions carefully before installing this unit. FAILURE TO ADHERE TO THESE
INSTRUCTIONS COULD RESULT IN SERIOUS BODILY INJURY OR PROPERTY DAMAGE.

STEAM PIPING INSTALLATION OF A SINGLE UNIT

Single and Double Wall

NOTE: FLO-RITE TEMP is provided with (1) one Armstrong Steam Trap and Thermostatic
Air Vent (shaded). All other items shown not included.
NOTE: units may be piped in parallel for larger capacity requirements. See Fig. 15-1 for an example of
parallel unit installation.
The unit includes the mixing valve mounted to the heat exchanger, channel iron and U-bolts mounted,
thermostatic air vent installed on the heat exchanger, a water pressure pop off valve integral to the unit control
valve and a separate Armstrong Inverted Bucket Steam Trap.
1.
Install the FLO-RITE-TEMP with adequate room to allow for tube bundle removal when cleaning is
required. See Table 12-1 for specific dimensions.
2.
If 2-15 psig of steam is available a pressure reducing valve is NOT required. If a pressure reducing valve is
required, an Armstrong Inverted Bucket Steam Trap is recommended to drain condensate at the inlet of the
pressure reducing valve.
October 31, 2002 @ 3:15 pm
FLO-RITE-TEMP

INSTANTANEOUS WATER HEATER

NOTICE
Steam
In
Armstrong Pressure
Reducing Valve (If Req'd)
GP-2000
Armstrong
I.B. Trap
Armstrong Thermostatic
Air Vent
2-15 psig Steam
in the Shell
Vacuum Breaker
Armstrong
I.B. Trap
STEAM SIDE INSTALLATION
(Refer to Fig. 2-1)
Safety Relief
Valve
Gate
Valve
Pressure
Gauge
Fig. 2-1
2