Armstrong Air BCE3M 24 Installation Instructions Manual - Page 7

Browse online or download pdf Installation Instructions Manual for Air Handlers Armstrong Air BCE3M 24. Armstrong Air BCE3M 24 18 pages. Bce3m series; bcs3m series

IMPORTANT
On units of this type, where the blower "draws" rather than "blows" air through the coil, traps must be installed in the
condensate drain lines (primary and auxiliary, if used). Traps prevent the blower from drawing air through the drain
lines into the air supply.
Typical Main and Overflow Drain
Figure 9
507120-01
Issue 1324