DISCOVER DRY CELL Operating Manual - Page 7

Browse online or download pdf Operating Manual for Camera Accessories DISCOVER DRY CELL. DISCOVER DRY CELL 11 pages. Valve regulated lead acid battery

DISCOVER DRY CELL Operating Manual

4.1 Charging

4.1.1 Charge Curve

A battery charge profile (also known as an algorithm) contains all of the logic used to execute a multi-stage charging
process, including the bulk, absorption and float phases. Charge profiles differ depending on the battery type, capacity,
battery manufacturer, and even the application. It is extremely vital that a battery is charged with an appropriate charge
profile. Not doing so, may cause the battery pack to be chronically under- or over- charged, resulting irreversible damage
and premature end-of-life.
The Bulk charge accounts for charging the battery from anywhere between 0% up to 80% state of charge. The absorption phase
charges the battery from 80% to nearly 100% state of charge. Lastly, a float charge supplies a controlled voltage and amperage
to bring the battery to a complete full charge. Without a float charge, recharge can be terminated based on time (this will need to
be determined as it will vary with depth of discharge and charge current) or percentage recharge (105%-108%).
To maximize battery life, a voltage regulated charger with temperature compensation is strongly recommended. The
voltage settings displayed in charge algorithm graph and charge setting tables, corresponds to the set points at 25°C
(77°F). For temperatures below 25°C, adjust +0.005VPC/°C (or 0.003VPC per °F). For temperatures above 25°C, adjust
-0.005VPC/°C (or 0.003VPC per °F). As the temperature decreases, the voltage should increase and vice versa.
If the charger has a preset charge profile for AGM type batteries, verify that these settings follow recommended charge
settings.
7
▲ CAUTION!
Always make sure the charger is in the correct setting and
compatible with the battery's charging requirements; never
charge a visibly damaged battery; never charge a frozen battery.
Acceptable charging AC ripple voltages shall be less than 4%
peak to peak ripple voltage (less than 1.5% rms voltage) of the
DC System voltage with duration of less than 6 milliseconds.
▲ WARNING!
Do not equalize charge DRY CELL Solar batteries! Equalizing is
an "over voltage-over charge" performed on flooded leadacid
batteries after they have been fully charged.
∆V=(T-25°C) x (
If a temperature sensor is not used, you must manually
adjust charging voltages based on the battery temperature
when in use.
▲ NOTE!
-0.005VPC
)
°C
▲ NOTE!