Camille Bauer SINEAX F534 Operating Instructions Manual - Page 9
Browse online or download pdf Operating Instructions Manual for Transducer Camille Bauer SINEAX F534. Camille Bauer SINEAX F534 12 pages. Transducer for measuring frequency
Operating Instructions
Transducer for measuring frequency SINEAX F534
Safety precautions to be strictly observed are marked
with following symbols in the Operating Instructions:
The instruments must only be disposed of
in the correct way!
Contents
1. Read fi rst and then ... ................................................ 9
2. Brief description .......................................................... 9
3. Technical data ............................................................. 9
4. Mounting ................................................................... 10
5. Electrical connections ............................................... 10
6. Commissioning and maintenance ............................. 11
7. Releasing the transducer .......................................... 11
8. Dimensional drawing ................................................. 11
9. Instruments admissions ............................................ 11
10. Declaration of conformity .......................................... 12
1. Read fi rst and then ...
The proper and safe operation of the device
assumes that the Operating Instructions is read
carefully and the safety warnings given in the
various Sections
4. Mounting
5. Electrical connections
are observed.
The device should only be handled by appropriately trained
personnel who are familiar with it and authorised to work
in electrical installations.
Unauthorized repair or alteration of the unit invalidates
the warranty.
2. Brief description
The transducer SINEAX F534 is intended for frequency
measurement. The instrument change the measured value into
a proportional load-independent DC current or DC voltage.
3. Technical data
Measuring input
Measuring range:
f
a
f
a
f
a
f
e
≥ 10 Hz, f
≤ 1500 Hz
e
/(f
-f
) < 50
e
a
: Measuring range start
frequence
: Measuring range end frequence
Nominal frequency:
See type label
Nominal input
voltage:
10 - 230 or > 230 - 690 V
Measuring output
DC current:
0(0.2) - 1 to 0(4) - 20 mA
± 1 to ± 20 mA
Load voltage:
- 12 V / 15 V
External resistance:
R
resp. ≤
I
AN
DC voltage:
0(0.2) - 1 to 0(2) - 10 V
± 1 to ± 10 V
Load capacity:
Max. 4 mA
Response time:
2 / 4 / 8 / 16 periods of the measuring
frequency
Power supply
AC/DC power pack (DC or 50/60 Hz)
Rated voltage
85 - 230 V DC / AC
24 - 60 V DC / AC
Power consumption:
3 VA
Options
Connected to the low
tension terminal side:
24 V AC or 24 - 60 V DC,
see Fig. 4
Power supply from
measuring input
(self powered):
24 - 60 V AC or
85 - 230 V AC, see Fig. 3
Please note the max. and min. measuring input
voltage!
Input voltage
Type label
range
inscription
= internal power
supply range
Self powered
by 1/2
24 - 60 V AC
(int. 24-60 V)
Self powered
by 1/2
85 - 230 V AC
(int. 85-230 V)
Accuracy (acc. to EN 60688)
Reference value:
Output span
Basic accuracy:
Class 0.2
Safety
Pollution degree:
2
Installation category:
III
15 V
max. [kΩ] ≤
I
[mA]
ext
AN
- 12 V
- I
[mA]
AN
= Full scale output
Tolerance
DC - 15 to + 33%
AC ± 15%
Power
supply
Tolerance
connec-
tion
Internal
measu-
± 15%
ring
input
9