esera 1-Wire Multisensor Pro II User Manual - Page 4
Browse online or download pdf User Manual for Accessories esera 1-Wire Multisensor Pro II. esera 1-Wire Multisensor Pro II 8 pages. Professional in-wall room sensor for temperature, air humidity and air quality (voc)
Air Quality Sensor (VOC)
Measuring range
Accuracy
Data output
Interface
Connection
1-Wire interface
Operating voltage
Current consumption
5
Ambient conditions
Protection system
Protection class
Temperature,Operation
Air Quality Sensor
Air Humidity
Storage temperature
Dimensions (outside)
6
Conformity
EN 50090-2-2
EN 61000-4-2, ESD
EN 61000-4-3, HF
EN 61000-4-4, Burst
EN 61000-4-5, Surge
EN 61000-6-1, interference immunity
EN 61000-6-3, interference radiation
RoHS/REACH
7
Software / control
The 1-Wire Multisensor Pro II is read out via 1-Wire command for DS2438 devices. The Multisensor is
supported in many controllers, such as ESERA-Station, Loxone, IP-Symcon, OWFS, FHEM, (Linux) or
microcontroller applications.
For ESERA 1-Wire Multisensor of the Pro Series no complex formulas are necessary anymore.
A sensor controller within the Multisensor takes over the preprocessing of all measured values and thus
simplifies the integration into 1-Wire systems enormously. Complex formulas are no longer necessary.
Also, the measured values are no longer dependent on the operating voltage of the 1-Wire Multisensor.
The sensor measurement values are assigned to the standard DS2438 device values (according to the data
sheet) as follows:
VDD = operating voltage (5V), VAD = humidity, Xsens = air quality.
Calculations:
Temperature:
Standard output according to DS2438 module
Operating voltage:
Standard output according to DS2438 module
Air Humidity:
To obtain the rel. humidity in percent, multiply the output value (Vas) by a factor of 10.
0.1V corresponds to 1% relative humidity
Air quality:
The air quality is output in accordance (equivalent) to CO2 sensors.
After start-up, the sensor outputs 0V for a few minutes. This means that the air quality sensor is in the start-
up phase.
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH 2021
www.esera.de
mixed gas sensor (VOC)
400 - 1800 ppm (CO2 equivalent)
+/- 10%, depending on air composition
30-250mV corresponds to 400-2900ppm, 1mV output voltage
corresponds to 11,6ppm. Smallest output value: 30,51mV
corresponds to 405ppm.
3 - conductor connection (Data, Ground and 5V, Parasitic operation not
supported).
Push-In terminals for cable solid 0.2 to 2.5qmm or
fine stranded 0,2 to 1,5qmm. For the connection we recommend
slotted screwdriver size 2,5x75
based on DS2438 command set
5 V= (+10%/-20%)
ca. 20mA
IP20
III
-25°C to 50°C, (Limitation of max. temperature to 50°C by air quality
sensor and sensor housing)
operating range 0 bis 50°C
5 to 95% (non condensing)
-25°C to 50°C
71 x 71 x 32mm (LxWxH)
11165 V1.0 R1.1 Manual
Page 4 of 8