7. Programming instruction
Control panel:
The inclination transmitter is programmable via keypad. The keyboard
is visible after opening the blue cover.
Modus:
The transmitter remains in programming mode for 60 minutes. If no key
is pressed during this time, the transmitter will exit the programming
mode without storing the programmed data.
Standard programming I (programming start and end value)
Application:
The measuring range (e.g. 4 - 20 mA) is between two fixed
tilt angles (e.g. – 10° to +  60°). The final position can be pro-
grammed via keystroke after mounting the KINAX on the aligned
object. The instrument can be electrically connected in any position.
y
+60°
20 mA
1. Programming mode «on»
press quickly: 2x red (R; R; ...LED on)
2. Put transmitter into initial position (+60°; 4 mA)
programming 0%
press quickly: 1x left green (0%; ...LED flashes 1 s)
3. Put transmitter into final position (-10°; 20 mA)
programming 100%
press quickly: 1x right green (100%; ...LED flashes 1 s)
4. Switch sense of rotation (optional) (-10°; 4 mA)
press quickly: 1x red (R; ...LED flashes 1 s)
5. Programming mode «off»
press quickly: 2x red (R; R; ...LED flashes1 s, LED off)
PM 1002077 000 00
LED
green button
Red button
α
x
–10°
4 mA
Inclination transmitter KINAX N705-MEMS 4...20 mA
Standard programming II (Zero position programming)
Application:
The measuring range (e.g. 4 - 20 mA) is adjusted by factory and
symmetrically split (e.g. ± 45°). The range is calibrated on factory side
and should not be changed. The initial position can be programmed
via keystroke after mounting the KINAX on the aligned object. The
instrument can be electrically connected in any position. The adjusted
measuring range is symmetrical and starts from zero position, e.g. the
zero position corresponds always to 12 mA.
.
+45°
1. Programming mode «on»
press quickly: 2x red (R; R; ...LED on)
2. Programming zero position
press quickly: 1x green left & right (0% & 100%; ...LED flashes 1 s)
3. Switch sense of rotation (optional)
press quickly: 1x red (R; ...LED flashes 1 s)
4. Programming mode «off»
ress quickly: 2x red (R; R; ...LED flashes 1 s, LED off)
To restore the factory settings (RESET):
1. Programming mode «on»
press quickly: 2x red (R; R; ...LED on)
2. Keep red key pressed (> 3 s)
(R; ...LED flashes 1 s; LED off)
-45°
Position of the
cable feeder
arbitrary
12/12