Camille Bauer SINEAX V604s Safety Instructions - Page 3
Browse online or download pdf Safety Instructions for Transmitter Camille Bauer SINEAX V604s. Camille Bauer SINEAX V604s 13 pages. Universal signal converter
Also for Camille Bauer SINEAX V604s: Operating Instructions Manual (19 pages)
Safety instructions which have to be observed without fail are
marked with the following symbols in these instruction:
Instruments may only be disposed of in a technically
appropriate manner!
Read first, then ...
The unobjectionable and safe operation presup-
poses that these safety instructions as well as
the operating instructions have been read and
understood!
This instrument should only be handled by re-
spectively trained staff members who know the
instrument and are authorised to work on techni-
cal facilities.
The operation of the instrument must be stopped
if its safe operation (e.g. in case of visible damage)
is not possible any more. All connections are to
be disconnected in this case. The instrument is
to be forwarded to our plant or a service station
authorised by us.
Any warranty claim lapses if the instrument is
opened!
www.camillebauer.com/vx604s-en
Scope of delivery
1 SINEAX V604s, VB604s or VQ604s
1 Safety instructions 168 501
Brief description
SINEAX V604s, VB604s or VQ604s is a programmable multifunctional
transmitter for top-hat rail assembly. Input, output, bus and power sup-
ply are galvanically isolated.
Programming and communication are arranged via a Modbus interface.
Technical data
Measuring input
2 measuring inputs galvanically connected. In case of 2 sensors, observe
wiring instructions in the operating instructions!
Type of measurement
Measuring range
DC voltage [mV]
–1000 ... 1000 mV
DC voltage [V] *
–600 ... 600 V
DC current [mA]
–50 ...
Resistance [Ω]
0 ... 5000 Ω
RTD Pt100
–200 ... 850 °C
RTD Ni100
–60 ... 250 °C
TC Type B
0 ... 1820 °C
TC Type E
–270 ... 1000 °C
TC Type J
–210 ... 1200 °C
TC Type K
–270 ... 1372 °C
TC Type L
–200 ... 900 °C
TC Type N
–270 ... 1300 °C
TC Type R
–50 ... 1768 °C
TC Type S
–50 ... 1768 °C
TC Type T
–270 ... 400 °C
TC Type U
–200 ... 600 °C
TC Type W5Re-W26Re
0 ... 2315 °C
TC Type W3Re-W25Re
0 ... 2315 °C
* not at VB604s and VQ604s
1)
In older device versions the measuring range is only -300 ... 300V. Before using,
please check the device version on the nameplate or with the CB-Manager SW
Camille Bauer Metrawatt AG
Minimum span
2 mV
1)
>1 V
50 mA
0.2 mA
8 Ω
20 K
15 K
635 K
34 K
39 K
50 K
38 K
74 K
259 K
265 K
50 K
49 K
135 K
161 K
Safety instructions V604s, VB604s and VQ604
Safety Instructions
Camille Bauer Metrawatt AG
Aargauerstrasse 7
CH-5610 Wohlen/Switzerland
Phone +41 56 618 21 11
Fax
+41 56 618 21 21
www.camillebauer.com
Outputs
2 analog outputs, galvanically connected, common earth. Voltage or
current output of V604s/VB604s can be configured by software, the
VQ604s only in corresponding device type.
Direct
Range ±20 mA, burden voltage 12 V
current
Open circuit voltage < 20 V
Limitation max. ±22 mA
Direct
Range ±10 V,
voltage
load max.: V604s/VB604s: 20 mA, VQ604s: 0.02 mA
Current limitation approx. 30 mA
Limitation max. ±11 V
Relay contact output
Version relay
Contact
1 pole, normally open contact (NOC)
Switching capacity AC: 2A/250V, DC: 2A/30V
Version digital output*:
Contact
Transistor, normally open contact (NOC)
Switching capacity max. 27VDC/27mA
Bus/ programming connection
Interface, protocol
RS485, Modbus RTU
Power supply
Rated voltage U
N
24 ... 230 V DC *
100 ... 230 V AC, 50/60 Hz
Green LED = «Power ON» display
*
In case of a power supply voltage > 125 V DC, the power supply
circuit must contain an external fuse.
Electrical connections
Pluggable screw or spring cage terminals serve the connection of elec-
tric lines. They are suitable to wire cross-sections up to max. 2.5 mm
Ensure without fail that all lines are not under load
during connection!
Possibly impending danger from high voltages.
Please observe ...
... that the data on the name plate are adhered to!
Arrange a marked, easily accessible switch in the vicinity of the
instrument to deactivation of the power supply.
As the power supply is switched on, the power supply source must
provide sufficient current (approx. 0.3 A) for a brief period of time.
Furthermore, the national provisions (e.g. for Germany VDE 0100
«Conditions concerning the erection of electric power installations
with rated voltages below 1000 V») are to be followed in the instal-
lation and selection of the material of electric lines!
SINEAX V604s,
VB604s, VQ604s
Universal
Signal Converter
168 501-05
06.17
PM1000752 000 01