esera automation 11150 User Manual - Page 4
Browse online or download pdf User Manual for Accessories esera automation 11150. esera automation 11150 7 pages. 1-wire multisensor pro for temperature and air humidity
5
Conformity
EN 50090-2-2
EN 61000-4-2, ESD
EN 61000-4-3, HF
EN 61000-4-4, Burst
EN 61000-4-5, Surge
EN 61000-6-1, interference immunity
EN 61000-6-3, interference radiation
RoHS
6
Software / Control
The 1-Wire Multisensor Pro is read out via 1-Wire command for DS2438 modules. The sensor is supported by
many controllers like ESERA-Station, Loxone, IP-Symcon, OWFS, FHEM, (Linux) or Micro Controller
applications.
For ESERA 1-Wire Multisensors of the Pro series no complex formulas are necessary anymore.
A sensor controller within the Multisensor takes over the preprocessing of all measured values and thus simplifies
the integration into 1-Wire systems enormously. Also, the measured values are no longer dependent on the
operating voltage of the 1-Wire Multisensor.
The sensor measured values are assigned to the standard DS2438 device values as follows:
VDD = operating voltage (5V), VAD = humidity, Xsense = no data output, fixed at 0
Calculations
Temperature
Standard output according to DS2438 module
Operating voltage
Standard output according to DS2438 module
Humidity
To obtain the rel. humidity in percent, multiply the output value (Vas) by a factor of 10. 0.1V corresponds to
1% relative humidity.
7
Data output 1-Wire Controller / 1-Wire Gateway
For the 1-Wire Multisensor Pro, the following measured values are calculated and output by the 1-Wire
Controller / 1-Wire Gateway. The dew-point calculation is a function of the 1-Wire Controller /
1-Wire Gateway.
Data output:
1_EVT|12:27:40
1_OWD1_1|2008
1_OWD1_2|511
1_OWD1_3|470
1_OWD1_4|1200
Further information for options and commands can be found in the latest available documentation for
1–Wire Controller / 1–Wire Gateway.
8
Integration in IP-Symcon / ESERA-Station
Through our website we provide ESERA IP-Symcon software-modules to import the 1-Wire Multisensor in
IP-Symcon via 1-Wire Controller / 1-Wire Gateway. Therefore, no scripts are necessary.
Details can be found on the ESERA website at :
symcon-integration/.
For conventional connection via 1-Wire Bus couplers, the sensor values must be calculated according to the
specified formulas.
9
Integration in Loxone
At our webshop we provide a sample project on how to import the 1-Wire Multisensor by 1-Wire Controller
1/1-Wire Gateway. Further details can be found here:
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH 2021
www.esera.de
=> controller no._module no._data set|temperature (°C) example: 20,08 °C
=> controller no._module no._data set |voltage VCC (V)
=> controller no._module no._data set|humidity (rF) example 47,0%
=> controller no._module no._data set|dew point (°C) example: 12,00 °C
11150 V3.0 R1.0 Manual