Browse online or download pdf User Manual for I/O Systems esera automation 11229 V2. esera automation 11229 V2 6 pages. 8-fold digital output / switching module / binary output 8 x 8a for 1-wire bus system w/auto-e-connect

esera automation 11229 V2 User Manual
3
Auto-E-Connect® Support
The ESERA Auto-E-Connect® 1-Wire Plug and Play system will be used for the
1-Wire Bus supported. This enables fully automatic configurations of 1-Wire sensors
and actuators on the 1-Wire bus. It is optimized for industrial applications and
enables significant added value beyond the sensor and chip data.
The Auto-E-Connect function automatically recognizes ESERA chips, sensors and actuators, starts suitable
libraries and outputs fully formatted data.
The Auto-E-Connect functionality will be available from mid 2020 via 1-Wire Controllers, 1-Wire Gateways and
1-Wire ECO from ESERA available.
Further information on ESERA Auto-E-Connect can be found on the ESERA website, ESERA Config-Tool 3, or in
the download area for this article in the ESERA Webshop.
4
Technical data
Switching channels:
Switching voltage:
Switching current/power: Max. 8A continuous current per output and max. 1840VA continuous power with
Fuses:
Data interface:
1-Wire device:
Operating voltage:
Current consumption 12V: Rest state, no output relay active: approx. 10mA
Connection:
5
Ambient conditions
Temperature, operation: -20°C to +60°C
Humidity:
Dimensions:
Protection class:
Protection type:
Insulation strength:
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de
8, make contact (relays NO contact)
Max. 250V, DC or AC voltage
resistive load. Minimum load 10mA.
Max. 10A total current for all outputs
For capacitive or inductive loads, appropriate additional circuits, e.g. spark quenching
capacitors, must be provided. The max. current and the power are reduced.
External back-up fuse with 10A recommended
1-Wire bus (12V, data and ground),
DS2408 (8-fold I/O)
12VDC (+/-10%)
All outputs active: approx. 160mA (max. 1.9W)
Screw terminals (up to 2.5qmm cable cross-section)
10 - 92% (non-condensing)
70 x 90 x 70mm (WxHxD)
II
IP20
500VAC output to 1-Wire Bus