dixell COOL MATE XLR470 Operating Manual - Page 8

Browse online or download pdf Operating Manual for Temperature Controller dixell COOL MATE XLR470. dixell COOL MATE XLR470 18 pages. Dual temperature controller

dixell COOL MATE XLR470 Operating Manual
dIXEL
dIXEL
dIXEL
dIXEL
COF2 Compressor2 OFF time with faulty probe2: (0÷255 min) time during which the compressor is off in case of faulty thermostat probe. With
COF=0 compressor2 is always active.
CH2
Kind of action for section 2: CL = cooling; Ht = heating
DISPLAY
CF
Temperature measurement unit: °C = Celsius; °F = Fahrenheit. When the measurement unit is changed the SET point and the values of
some parameters have to be modified.
rES
Resolution (for °C): (in = 1°C; de = 0,1°C) allows decimal point display. dE = 0,1°C; in = 1 °C
Lod1
Bottom display visualization (section 1): select which probe is displayed by the instrument in the bottom display: P1 = Thermostat 1
probe; P2 = Evaporator 1 probe; P3 = Thermostat2 probe; P4 = Evaporator 2 probe
Lod2
Upper display visualization (section 2): select which probe is displayed by the instrument in the upper display: P1 = Thermostat 1 probe;
P2 = Evaporator 1 probe; P3 = Thermostat2 probe; P4 = Evaporator 2 probe
DEFROST
dFS
Relation between defrosts.4 relation between the 2 sections of the controller are available, to manage different kinds of applications: in =
independent defrosts; StS = same defrost start, synchronised defrost end; St = same defrost start, independent defrost end; SE = sequential
defrost;
tdF1
Defrost type, section 1: rE = electrical heater (Compressor OFF); in = hot gas (Compressor and defrost relays ON)
EdF1
Defrost mode, section 1: in = interval mode. The defrost starts when the time "IdF1" is expired.
Sd = Smartdefrost mode. The time IdF (interval between defrosts) is increased only when the compressor is running (even non
consecutively);
rtc (only for instruments with RTC): beginning of defrost cycles is set by the L1d1÷L1d6 parameters during the working days and
S1d1÷S1d6 during the holidays
Set point for SMARTDEFROST, section 1: (-30
SdF1
defrosts) in SMARTDEFROST mode.
dtE1
Defrost termination temperature, section 1: (-50,0÷110,0°C; -58÷230°F) (Enabled only when the evaporator probe is present) sets the
temperature measured by the evaporator probe which causes the end of defrost.
IdF1
Interval between defrosts, section 1: (1÷120h) Determines the time interval between the beginning of two defrost cycles.
MdF1 (Maximum) duration of defrost, section 1: (0÷255 min) When P2P = no, no evaporator probe, it sets the defrost duration, when P2P =
yES, defrost end based on temperature, it sets the maximum length for defrost.
tPF1
Pre-defrost time: (0÷30min) The compressor is activated for this time before a hot gas defrost.
Fdt1
Drain down time, section 1: (0÷60 min.) time interval between reaching defrost termination temperature and the restoring of the control's
normal operation. This time allows the evaporator to eliminate water drops that might have formed due to defrost.
dPo1
First defrost after start-up, section 1: y = Immediately; n = after the IdF time
Defrost type, section 2: rE = electrical heater (Compressor OFF); in = hot gas (Compressor and defrost relays ON)
tdF2
EdF2
Defrost mode, section 2: in = interval mode. The defrost starts when the time "IdF1" is expired.
Sd = Smartdefrost mode. The time IdF (interval between defrosts) is increased only when the compressor is running (even non
consecutively);
rtc (only for instruments with RTC): beginning of defrost cycles is set by the L1d1÷L1d6 parameters during the working days and
S1d1÷S1d6 during the holidays
SdF2
Set point for SMARTDEFROST, section 2: (-30
between defrosts) in SMARTDEFROST mode.
dtE2
Defrost termination temperature, section 2: (-50,0÷110,0°C; -58÷230°F) (Enabled only when the evaporator probe is present) sets the
temperature measured by the evaporator probe which causes the end of defrost.
IdF2
Interval between defrosts, section 2: (1÷120h) Determines the time interval between the beginning of two defrost cycles.
MdF2 (Maximum) duration of defrost, section 2: (0÷255 min) it sets the defrost duration.
tPF2
Pre-defrost time: (0÷30min) The compressor 2 is activated for this time before a hot gas defrost.
Fdt2
Drain down time, section 2: (0÷60 min.) time interval between reaching defrost termination temperature and the restoring of the control's
normal operation. This time allows the evaporator to eliminate water drops that might have formed due to defrost.
dFd
Display during defrost: rt = real temperature; it = temperature reading at the defrost start; Set = set point; dEF = "dEF" label; dEG = "dEG"
label;
dAd
Defrost display time out: (0
display.
dSd
Start defrost delay : ( 0÷99min) This is useful when different defrost start times are necessary to avoid overloading the plant.
FANS – Section 1
FnC1 Fan operating mode, section 1: C-n = running with the compressor1, OFF during the defrost; C-y = running with the compressor1, ON
during the defrost; O-n = continuous mode, OFF during the defrost; O-y = continuous mode, ON during the defrost;
Fnd1
Fan delay after defrost, section 1: (0÷255 min) The time interval between the defrost end and evaporator 1 fans start.
FSt1
Fan stop temperature, section 1: (-50÷110°C; -58÷230°F) setting of temperature, detected by evaporator probe, above which the fan is
always OFF.
FAP1 Probe selection for fans management, section 1: nP = no probe: fan follows the setting of FnC1 parameter; P1 = thermostat 1 probe; P2
= evaporator 1probe; P3 = thermostat 2 probe; P4 = evaporator 2probe;
FANS – Section 2
1592017050 XLR470 GB r1.0 24.05.07.doc
Operating manual
30 °C/ -22
÷
30 °C/ -22
÷
255 min) Sets the maximum time between the end of defrost and the restarting of the real room temperature
÷
86 °F) evaporator temperature which allows the IdF counting (interval between
÷
86 °F) evaporator temperature which allows the IdF2 counting (interval
÷
XLR470
cod. 1592017
cod. 1592
cod. 1592
cod. 1592
017050
017
017
050
050
050
8/18