DBC 3" Series Dry Disconnects
8. Remove all pressure from the coupler and remove from the water.
9. Install a Dry Disconnect Adapter equipped with a plug in its
threaded end. Make sure both CAM ARMS are closed and locked.
10. Rotate the LEVER to its open position and apply between 3
P.S.I.G. and 5 P.S.I.G. to the coupler.
11. Submerge under water and check for leaks at the MAIN
GASKET. (Coupler to Adapter interface) DO NOT CLOSE LEVER!
12. Increase pressure to 30 P.S.I.G. while still under water and check
for leaks at the MAIN GASKET. (Coupler to Adapter interface) DO
NOT CLOSE LEVER!
13. Remove all pressure from the coupler. Remove from the water.
Disconnect the air line from the test plug in the coupler.
14. Rotate the Lever to the closed position.
15. Unlock and open the CAM ARMS and remove the Dry Disconnect
Adapter.
10