AKKAYA-BLOWTHERM SBK-YSB-HYB User Manual - Page 18
Browse online or download pdf User Manual for Boiler AKKAYA-BLOWTHERM SBK-YSB-HYB. AKKAYA-BLOWTHERM SBK-YSB-HYB 20 pages. Steam boilers
CLEANING OF THE GAS SIDE
Opening fumes box's doors and connectings of burner is supplied to
determineand solve dirties that are became over the boiler.
If soots layeris less than 0,5mm,you don't need to clean it.
Soot or dirt layer must be cleaned wit special boiler pipe brush.
Thick soot layer cause to drop eficieny of the boiler.
Hard layers can be seen on the weited heat surface by companents of soot
and sulfur in the boiler that is worked very often in cold condition.
These layers are dangerous for the boiler's materials.
It must be cleaned in a very short time.It is not enough to clean with normal
fume pipes' brush
A special cleaning equipments with electricity motor and special,playing
heads are used for cleaning.
Before closing front doors again,MOLYKOTE must be applied on bolt
and nuts.
CLEANING WATER SIDE
Man holes must be used to determine sediments on the water side.
The lime layer which is nearly 1mm on the water side of the boiler,not only
drops the efficiency but also causes excess heatúng of materials .
Practisally,If you feed right feed water,to the boiler,lime formation on the
heating surface will not occur.
In this case,the boiler must be cleaned with pressured water,If there is still lime
in the boiler .You must clean with chemical cleaner.
Conderated water must always be controlled whiter it incluedes oil or not.You have
to be careful about oil existing on the heating surface of the boiler.
28
PROTECTION THE BOILERS
A) PROTECTING WATER SIDE OF THE BOILERFOR LONG PERIOD OF TIME
If the boiler won't be used for along time,you should make the following processes
to protect it from rust and corrosion;
Turnace;fumes pipes and fume gas side of miror plates must be cleaned at the
boiler temperature approx 40°.
All surfaces of gas side of the boiler are cleaned with oil to prevet it to get in ouch
with air.
The air must be dried by putting air drier chemicals in the boiler.
B) PROTECTING WATER SIDE OF THE BOILER FOR SHORT PERIOD OF TIME
During the boiler is out of service,the boiler have more rust and corrosion than
during the boiler is in service.
If there is water with a little alkali and water with pas in the boiler,rust and
corrosion emiloccur in the boiler.
If you don't take enough precautious for the boiler,even you discharge all water
from the boiler,corrosion will be seen.
The boiler with no water can be prevented from corrosion.
külfetle korozyona karúÕ korumak mümkündür.
THE BOILER OUT OF SERVICE FOR ONE DAY
You must clase all the steam and the water valves on the boiler.
Before stopping the boiler,
You must mix high quantity sodium carbonate and sodium sulp hide to the boiler
water for oxygen compound.
THE BOILER OUT OF SERVICE FOR ONE WEEK
The quantity of phosphate of the boiler water is raised by mixing 600 gr trisodium
phosphate per m³.
29