Altronix AL1012ULX Series Installation Manual - Page 5
Browse online or download pdf Installation Manual for Power Supply Altronix AL1012ULX Series. Altronix AL1012ULX Series 8 pages. Power supply/charger
AL1012ULXB - Power Supply Board
Terminal Legend Function/Description
L, N
Connect 115VAC to these terminals: L to Hot, N to Neutral. Do not use the [G] terminal.
– DC +
12VDC @ 10A continuous non power-limited output.
Indicates loss of AC power, e.g. connect to annuciator/alarm panel. Relay normally ener-
gized when AC power is present. Contact rating 1A @ 30VDC. AC Fail condition will
AC FAIL
report approximately one (1) to one minute after loss of AC. To delay report for 6 hours
NC, C, NO
cut jumper J1 on the Power Supply Board (AC trouble output delay option). If this mode is
selected, the Power Supply Board must be reset by removing all power to it for 30 seconds.
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized
BAT FAIL
when DC power is present. Contact rating 1A @ 30VDC. Low battery conditions will
NO, C, NC
report approximately 10.5VDC. Battery presence detection will report approximately 1
minute after battery remains undetected (missing or removed).
+ BAT –
Stand-by battery connections. Maximum charge rate 0.7A.
PD4/PD4CB/PD8/PD8CB - Power Distribution Module
Terminal Legend
PD4/PD4CB
1P to 4P
1N to 4N
Fig. 2a - PD4UL Power Distribution Board
Non Power-Limited Outputs
Replace fuses with the same type and rating 3.5A, 250V.
F1
F2
1P
1N
2P
2N
3P
DC Output to devices
(
1P-4P Power Outputs,
1N-4N Common Outputs
Fig. 3a - PD8UL Power Distribution Board
Non Power-Limited Outputs
Replace fuses with the same type and rating 3.5A, 250V.
1
2
3
4
5
P
FUSED
POWER
OUTPUTS
N
COMMON POWER OUTPUTS
DC Output to devices
(
1P-8P Power Outputs,
1N-8N Common Outputs
AL1012ULX Series
Terminal Identification:
PD8/PD8CB
1P to 8P
1N to 8N
Power Distribution Module(s):
F3
F4
LED
3N
4P
4N
From Power Supply
)
Board
(Factory Installed)
6
7
8
D1
LED
R1
INPUT
From Power Supply
)
Board
(Factory Installed)
Function/Description
Positive DC power outputs.
Negative DC power outputs.
Fig. 2b - PD4ULCB - Power Distribution Board
F1
1P
POWER OUTPUTS
Fig. 3b - PD8ULCB - Power Distribution Board
1
P
F U S E D
N
C O M M O N
(
Class 2 Power-Limited Outputs
F2
F3
1N
2P
2N
3P
3N
4P
DC Output to devices
(
)
1P-4P Power Outputs,
1N-4N Common Outputs
Class 2 Power-Limited Outputs
2
3
4
5
6
7
P O W E R
O U T P U T S
P O W E R
O U T P U T S
DC Output to devices
)
1P-8P Power Outputs,
1N-8N Common Outputs
F4
LED
4N
INPUT
From Power Supply
Board
(Factory Installed)
8
D1
LED
R1
INPUT
From Power Supply
Board
(Factory Installed)
- 5 -