Arthur Grillo DPC200 Installation And Operation Manual - Page 15

Browse online or download pdf Installation And Operation Manual for Controller Arthur Grillo DPC200. Arthur Grillo DPC200 16 pages. Differential pressure controller, low pressure sensor with pi-control-mode
Also for Arthur Grillo DPC200: Manual (7 pages), Installation And Operation Manual (14 pages)

Arthur Grillo DPC200 Installation And Operation Manual

10. Specifications

Specifications
Measuring medium:
Measuring principle:
Lowest span:
Highest span:
Overpressure protection:
Static pressure:
Pressure connections:
Case:
Supply voltage:
Current consumption:
Output:
Display:
Mode:
Controlling algorithm:
Set points:
Protection class:
Ambient temperature:
Weight:
Mounting:
Interference emission:
Influences limits:
Air or non-aggressive gases
Silicon diaphragm with spring and differential transformer
0...50 Pa
0...6000 Pa
0,2 bar
max. 0,2 bar
hose liners 5 mm ø and 6 mm ø
UL 94 HB; Case polyamid, cover ABS
10...30 Vdc or 24 Vac ± 15 %
Electronic protection against faulty polarization
ca. 10 mA @ 10 Vdc, ca. 12 mA @ 24 Vdc
0...10 V
Open Collector, max. 30 V / 30 mA
LCD-Display, 2x16 characters
Measuring mode or controlling mode
PI
2 set points adjustable within software,
Set points are selectable with floating contact input
IP 54 according EN 60529
0...+50 °C
approx. 90 g
vertical, position dependence by turning of 90°: approx. 25 Pa
According EN 50081-2, EN 50082-2, CE mark
Zero error:
Sum of linearity and hysteresis
(depends on measuring range):
Temperature drift, zero point:
Temperature drift, span:
Doc.-no.: DPC200_01_EN
GEWÄHRLEISTUNG & SUPPORT
(I
= 0,5 mA @ 10 Vdc, I
max
Issue: 11/2015
= 2 mA @ 20 Vdc)
max
± 0,75 %
± 0,5 %
± 0,3 % / 10 K
± 0,2 % / 10 K
15