Arthur Grillo DS200 Installation And Operation Manual - Page 10

Browse online or download pdf Installation And Operation Manual for Accessories Arthur Grillo DS200. Arthur Grillo DS200 16 pages. Differential pressure sensor

Arthur Grillo DS200 Installation And Operation Manual
OPERATION
5.2 Adjustable parameters - Software
Parameters
Unit
Parameter
K-factor:
Measurment
range:
Characteristic: linear or square rooted
Analogue
output:
Limit value:
alarm delay
time
Switching
logic
Contact logic Contact logic active high or active low
10
Selection or parameter range
metric or imperial
Differential pressure ΔP [Pa or InH
Volume flow V [m3/h or cfm]
Volume flow calculation according to: V = k · √Δp
with:
V = Volume flow in m
k = flow factor, adjustment range: 1...10,000
Δp = differential pressure in Pa or InH20
Calculation up to: 999,999 m
Maximum volume flow (V
Measuring range: 200 Pa, k=10.000
Measuring range: 1000 Pa, k=10.000
Measuring range: 6000 Pa, k=10.000
MBI
DS200-2 -
200 Pa
DS200-10 - 1.000 Pa
DS200-60 - 6.000 Pa 4.000 Pa 3.000 Pa 2.000 Pa
0...10 V / 0...20 mA or 2...10 V / 4...20 mA
Differential pressure from 0% up to 100% of
measuring range.
Volume flow from 5% up to 100% of measuring
range, k-factor is considered.
Switching delay time adjustment range:
1...60 seconds or 2....15 minutes
Switching logic MIN or MAX
Doc.-no.: DS200_01_EN
O]
2
/h or cfm
3
/h (587.999 cfm)
3
):
max
V
= 141.421 m
/h; (83.155 cfm)
3
max
V
= 316.228 m
/h; (185.942 cfm)
3
max
V
= 774.597 m
/h; (37.188 cfm)
3
max
MB2
MB3
150 Pa
100 Pa
500 Pa
300 Pa
Issue: 05/2017
Default
metric
differential
pressure
ΔP [Pa]
K = 70
MB4
50 Pa
MB1
200 Pa
linear
0...10 V /
0...20 mA
OFF
10 s
MAX
active high