Arthur Grillo DS85P Installation And Operation Manual - Page 9
Browse online or download pdf Installation And Operation Manual for Accessories Arthur Grillo DS85P. Arthur Grillo DS85P 10 pages. Differential pressure sensor
9. Disposal
When disposing of electronic components and devices, observe the legal regulations in
the country of use.
10. Technical specifications
Overload safety:
Static pressure:
Zero-point calibration:
Sum of linearity and
Temperature drift measuring
Operating mode:
Measuring sensor:
Measurement unit:
Smallest measuring span:
Largest measuring span:
Measuring ranges:
Measuring range selection:
Ambient temperature:
Storage temperature:
Protection class:
PERFORMANCE:
0,2 bar
Max. 0,2 bar
Adjustable via REED contact, no cyclic zero-point
calibration required
Reaction time:
Immediately
ACCURACY / ERROR LIMITS:
Zero offset:
See chapter 6. error limits
hysteresis:
See chapter 6. error limits
span:
Due to 4 measuring ranges in 3 measuring groups
TECHNICAL SPECIFICATIONS:
measurement mode
Medium:
Air or non-aggressive gases
Electromechanical diaphragm movement
Pa
0...50 Pa (0,5 mbar)
0...6000 Pa (60 mbar)
0...50 Pa (0,5 mbar), 0...200 Pa (2 mbar),
0...500 Pa (5 mbar), 0...1000 Pa (10 mbar),
0...2000 Pa (20 mbar), 0...4000 Pa (40 mbar),
0...6000 Pa (60 mbar)
Yes via 2-pole DIP switches
Characteristic:
Linear
-10...+50 °C
-25...+60 °C
PHYSICAL:
∅ 70 mm, depth 50 mm
Case:
Ultramid
Dimensions:
Weight:
approx. 90 g
IP 54 according EN 60529
Doc.-no.: DS85P_01_EN
issue: 09/2018
10