Altronix AL1002ADA220 Installation Manual - Page 8

Browse online or download pdf Installation Manual for Extender Altronix AL1002ADA220. Altronix AL1002ADA220 17 pages. Nac power extender
Also for Altronix AL1002ADA220: Application Manual (8 pages)

Altronix AL1002ADA220 Installation Manual
NEC Power-Limited Wiring Requirements for
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit
wiring must remain at least 0.25" away from any non power-limited circuit wiring. Furthermore, all power-limited
circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits.
One such example of this is shown below. Your specific application may require different conduit knockouts to
be used. Any conduit knockouts may be used. For power- limited applications use of conduit is optional. All field
wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute).
Optional battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods.
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 2a, pg. 8).
Fig. 2
220VAC Input
50/60Hz
(non power-
limited)
Aux. Output
(power-limited)
non-supervised
NAC Circuits
(power-limited)
supervised
Fig. 2a
Incorrect Wire
Handling
Wire
Insulation
Solid Copper
Conductors
- 8 -
AL1002ADA220 Models:
Battery
Connections
(non power-limited)
supervised
Correct Wire
Handling
External
Jacketed
Shield
Pull back
external jacketed
shield approx. 1/2".
Supervisory Connections
(power-limited)
non-supervised
Signaling
Circuits
from FACP
(power-limited)
supervised
AL1002ADA220 Installation Guide