CONDENSATE DRAIN

In the event of horizontal installation,
assemble the condensate discharge
connection
supplied.
Make sure you
seal the connection between the drip
tray and the fitting with silicone. The
condensate drain network must be
properly scaled and the piping situ-
ated in such a way as to keep an ade-
quate slope along the route (min. 1%).
ELECTRICAL WIRINGS
WARNING: check that the power sup-
ply is disconnected before carrying
out any procedures on the unit.
The unit must be connected directly
to an electrical outlet or to an
independent circuit.
install a device, main switch or plug
which allows to completely cut off
the power supply from the unit.
To protect the unit against short cir-
cuits, fit an omnipolar thermal-mag-
netic trip 2A 250V (IG) to the power
line with a minimum contact opening
distance of 3mm.
C H A R A C T E R I S T I C S
CONNECTION CABLES
Use H05V-K or N07V-K type cables
with 300/500 V with insulation, piped
or ducted.
All the cables must be piped or ducted
until they are inside the fan coil.

ROTATING THE COIL

If the hydraulic connections require the
rotation of the coil, remove the front
closure panel and proceed as follows:
- Remove the condensate drip tray;
- Undo the screws and remove the coil
cover;
- Remove the screws securing the coil,
then remove the coil;
- Remove the push-outs on the right-
hand side;
- Rotate the coil and secure it with the
previously removed screws;
- Reassemble the cover and fix it with
18
IFCXIUASLJ 1003 - 5383600_01
If condensate is discharged into the
sewage system, install a siphon to
prevent the return of unpleasant odours
into the room.
Carry out a functioning and seal test of
the condensate drain system by pour-
ing water into the tray
The cables coming out of the pipe or
duct must not be subject to stretching
or twisting. They must be protected
from external agents.
Stranded cables can only be used with
crimping terminals. Make sure that the
strands of the wires are inserted properly.
Wiring diagrams are constantly updat-
ed. It is therefore compulsory to refer
to the ones supplied with the unit.
The control panel may not be fitted on
a metal wall unless this is permanently
connected to an earthed outlet.
When using remote control panels,
O F
T H E
the relative wiring diagram must be
respected. Before installing the control
panel, read the instructions carefully
and configure the panel if necessary.
In installations with a three-way valve,
the minimum water temperature sen-
sor must be relocated from its standard
the screws;
- Reassemble the plastic plugs (supplied)
in the holes left free by the water
connections;
- All the trays can be used to collect
condensate on both sides. In case of
vertical installation, to discharge
condensate on the right side, position
the drain connection to the right.
- Slide out the electrical wirings from the
right-hand side, remove the push-out
and move the cable grommet from the
right to the left side;
mounting in the coil assembly to the
delivery hose upstream of the valve.
Connect the valve and sensor to the
control board, in the positions indi-
cated in the wiring diagram.
WARNING: check whether the instal-
lation has been carried out correctly.
Follow the checking procedures indi-
cated in the control panel manuals.
- Transfer the electrical wirings to the left
side through the cable grommet;
- Move the control board, the earthing
u-bolt and any electric devices to the
left-hand side.
4
7
11
10
9
Ø est. 20,5mm
5
6
3
8