6. After the circuit is checked "dead" and made certain that it is
maintained "dead", insert the insulated test probes into the Test ports.
With the grounding switch open, apply the test voltage to the cables via
the insulated test probes.
(C) For Phasing-Out
1. With the device out of the breaker compartment, correctly identify
Line and Bus Terminals for the Breaker Compartment and visually
make certain that the connections will be made to the Terminals.
2. Lift the device and load it onto the extension rails of the breaker
compartment with extreme care.
3. Push the device to the "Test" position as indicated by the crisp clicking
sound of the levering latch engaging the levering nut.
4. Using the breaker levering handle, lever the device to the "Connected"
position as indicated by the red flag appearing in front of and under the
levering crank.
5. Check the "Phasing Out" according to the specific customer's
operating procedure.