CVS Controls CVS1000L Product Manual - Page 9
Browse online or download pdf Product Manual for Valve Positioners CVS Controls CVS1000L. CVS Controls CVS1000L 13 pages. 1000l electro-pneumatic linear positioner

Adjustment - Span
1. After setting zero, supply 20mA or 4mA of signal.
Check the actuator's stroke. If the stroke is too low,
adjust the span towards the (+) direction.
If the stroke point is too high, adjust the span towards
the (-) direction. (Figure 18)
2. Changing span points affects the zero point setting,
so the zero setting must be set again. After setting
zero point, confirm the span point. This step must be
repeated until both points are properly set.
3. After setting is completed, tighten lock screw.
Lock Screw
Adjustment - A/M Switch (Auto/Manual)
1. A/M switch adjusts the valve operation to automatic
or manual.
2. When produced, YT-1000L is set at "A(Automatic)".
If user prefers the positioner setting as "M(Manual)",
the setting can be changed by turning the switch coun-
ter-clockwise. (Figure 19)
3. If it is set as "M(Manual)", the air pressure will be
supplied to the actuator directly. Always set back to
"A(Automatic)" after setting change.
4. If OUT2 in single acting actuator or double acting
actuator is used, the A/M switch will not operate.
Product Manual: CVS Rack & Pinion Actuator
Lock Screw
Auto Manual Switch
Adjustment - Seat Adjuster
1. Seat adjustment is set according to the customers
request before the positioner is delivered. Please do
not adjust the seat adjuster.
2. Seat adjuster is always used for double acting
actuators and adjusted when the pressure balance
point must be changed. Please do not touch the seat
adjuster, because it can affect the positioner's
performance.
Output
Pressure
Output
Pressure
Output
Pressure
Input Pressure
Adjustment - Orifice
1. If the size of the actuator is too small relative to the
flow rate, the positioner can have hunting. In order to
avoid hunting, orifice can be used. There are three
types of orifice.
9
CVS Controls Ltd.
Seat Adjuster
High Pressure Balance
(0.9~1.0Ps) - Normal
Balanced Point
Med. Pressure Balance
Balanced Point
(0.5Ps) - Normal
Balanced Point
Low Pressure Balance
(0.4~0.5Ps) - Normal
Ps=Supply Pressure
CVS Controls Ltd.
Process Management