AERMEC WRL 400 Installation & Maintenance Manual - Page 5
Browse online or download pdf Installation & Maintenance Manual for Chiller AERMEC WRL 400. AERMEC WRL 400 16 pages. Reversible / chiller - heat pumps
1.
RECEIPT OF THE PRODUCT AND
INSTALLATION
1.1.
RECEIPT AND HANDLING
The machine is sent from the factory wrapped with
estincoil placed on a loading pallet.
Before handling the unit, verify the lifting capacity of
the machines used.
Handling must be performed by qualified, suitably
equipped staff.
Handling the machine:
- Whenever it is envisioned to lift the machine
with belts, so as not to damage the structure,
place protections between the belts and the
framework. It is prohibited to stop below the unit
during lifting.
- The machine must always be kept in a vertical
position;
- The instructions found on the machine on an
integral part of the same. It is recommended to
read them and keep them with care.
- WARNING: The units CANNOT be stacked.
1.2.
SELECTION AND PLACE OF INSTALLATION
The WRL water/water INDOOR heat pump with
gas side inversion (R410A) is sent from the factory
already inspected and only requires electric and
hydraulic connections in the place of installation.
Before beginning installation consent with client and
pay attention to the following recommendations:
•
The support surface must be capable of
supporting the unit weight.
•
The safety distances between the units
and other appliances or structures must be
scrupulously respected.
•
The unit must be installed by a skilled tech-
nician in compliance with the national law
in force in the country of destination.
•
It is mandatory to foresee to the necessary
technical space in order to allow ROUTINE
AND EXTRAORDINARY MAINTENANCE in-
terventions.
Remember that whilst operational the chill-
•
er can cause vibrations; therefore "VT"anti-
vibration mounts (accessories) are recom-
mended, fixed on the base according to the
assembly layout.
•
Fix the unit, checking that it is level.
IWRLI2_13.04_5890700_00
1.3.
HANDLING
1.4.
MINIMUM TECHNICAL SPACES
600mm
23,6 in
600mm
23,6 in
600mm
23,6 in
600mm
23,6 in
THE UNIT HAS TO BE INSTALLED
IN TECHNICAL ROOMS,
OR ROOMS WHICH HAVE AT
LEAST A DRAIN ON THE FLOOR.
ATTENTION:
DRAWINGS ONLY INDICATIVE
5