Cylon CBX-8R8 Technical Datasheet And Installation Manual - Page 11
Browse online or download pdf Technical Datasheet And Installation Manual for Controller Cylon CBX-8R8. Cylon CBX-8R8 15 pages.
If you attempt to add more modules than the
will be displayed:
FLX
When the correct number of
modules has been added, enter a
and click
.
number
OK
Note: The IO module configuration can be changed later by opening the
dialog from the
Module Configuration
In the Strategy drawing, IO blocks can be added up to the total on the configured
FLX
CBX
modules plus the
onboard IO.
Note: If a
FLX
module is deleted from a
Strategy drawing has been set up, the blocks associated with that FLX's IO
will be 'greyed out' to indicate that they are inactive.
DS0119 rev 40
©2018 Cylon
CBX
can support, an error message
Device Instance
FLX
:
Site Tree
CBX
configuration (in CCConfig) after the
All Rights Reserved.
Subject to change without notice
5.4. Set up the Controller Strategy
HD
CXpro
In
, double-click on the controller in the
If there is no existing Strategy in the controller, an invitation to create a new one
will be displayed:
to open a new blank strategy drawing:
Click
Yes
Add strategy blocks and points to create the required strategy – see MAN0133
HD
CXpro
User Guide for more detail.
Note that in
CBX-8R8(-H)
controllers there are:
•
a total of 1024 strategy blocks, numbered 1 - 1024
•
a total of 1024 analog virtual points 1 - 1024
•
a total of 1024 binary virtual points 1 - 1024
•
a minimum of 16 and a maximum of 64 hardware points:
oThe first 16 are numbered 1-16, representing the internal I/O in the CBX
oThe 16 points in an attached
FLX
with MS/TP address set to "1" are numbered 101-116
oThe 16 points in an attached
FLX
with MS/TP address set to "2" are numbered 201-216
oThe 16 points in an attached
FLX
with MS/TP address set to "3" are numbered 301-316
WWW.CYLON.COM