Ashcroft A Series Installation And Maintenance Instructions - Page 4

Browse online or download pdf Installation And Maintenance Instructions for Switch Ashcroft A Series. Ashcroft A Series 4 pages. Miniature watertight pressure switches

Ashcroft A Series Installation And Maintenance Instructions
INSTALLATION
• To minimize the risk of injury, the switch enclosure must be
selected according to the area classification and installed
according to the required safety and electrical codes.
• Torque should always be applied to the Hex portion of the
body, never to any other part of the body for it may alter
the setpoint. It is recommended that Teflon tape or other
sealant be used on the threads prior to installing to prevent
leaks in the system.
• The ambient temperature limits for the switches are –40° to
100°C (varies with seal ordered).
• Switch should be protected from excessive shock and
vibration.
• The cover of the APA switch should be closed at all times
when the switch is in operation.
CAUTIONS
• Always close the cover of the APA switch after making any
setpoint adjustments.
• Do not exceed current or voltage limits.
• The protection degree of the switch is only valid when
the switch is installed in accordance with all safety and
electrical codes and regulations.
CLEANING
• Never use aggressive solvents.
• Do not use high pressure water to clean the switch.
For the name and location of the nearest sales
representative, contact the Stratford Office.
Ashcroft Inc.
250 East Main Street
Stratford, CT 06614
Tel: 203-378-8281
Fax: 203-385-0408
www.ashcroft.com
© 2022 Ashcroft Inc., 250 East Main Street, Stratford, CT 06614-5145, USA, Tel: 203-378-8281, Fax: 203-385-0357, www.ashcroft.com
All sales subject to standard terms and conditions of sale. I&M002-10038-10_00(250-3129) Rev. 03/22
MAINTENANCE/TROUBLESHOOTING
• All Ashcroft switches require little or no maintenance.
• Be sure the cover on the APA switch is closed at all times.
• When the switch is exposed to process media that may
harden and/or build up in the pressure port, the switch
should be removed and cleaned as required.
• If the switch does not function, only trained and skilled
personnel should check on the wiring, power supply and/or
mounting.
• If the problem cannot be solved, please contact one of the
Ashcroft affiliates or distributors.
FACTORY SETPOINTS
The APS switches and APA switches with a setpoint called
out in the product code are set at the factory as follows:
• Increasing Setpoint (R) Rising Pressure or Decreasing
Vacuum – Normally Open contact will close when the
pressure is raised from 0 psig to the setpoint. The
resetpoint is then measured from the setpoint, reducing the
pressure until the Normally Open contact opens.
• Decreasing Setpoint (D) Decreasing Pressure or Increasing
Vacuum – Normally closed contact will close when the
pressure is lowered from full range pressure to the setpoint.
The reset is then measured from the setpoint, increasing the
pressure until the Normally Closed contact opens.
Note: When ordered as a –15/15 psi range switch, depending
on setpoint, the Normally Open contact may be closed
as received.
Safety Manual and SIL Certificate, CRN available on
www.ashcroft.com