DOLD BL 5922 Safety Technique - Page 2

Browse online or download pdf Safety Technique for Measuring Instruments DOLD BL 5922. DOLD BL 5922 6 pages. Emergency-stop monitor

Application
Indication of the status of e-stop buttons in an e-stop chain. We recommend
to use the BH 5922 together with DOLD E-stop modules (approval).
Function
If all the e-stop buttons are closed all green LEDs are on. If one button is
activated the corresponding LED goes off.
The e-stop buttons are connected in series, therefore only one LED goes
off even if several buttons are pressed. Only the first activated button in
the row is indicated. When this e-stop button is released again the LED
lights up again and the LED of the next activated button in the row goes
off.
If the variant B_ 5922/0_2, B_ 5922/0_4, B_ 5922/0_5 is connected to a
IP 5503 in Plug and Play modus the outputs show the state of the E-stop
buttons an dthe LEDs the state of the status LEDs Ι1 - Ι8 on the e-stop
monitor.
Indicators
Green LED "On":
on, when supply connected
Yellow LED:
on, when bus active (only with /002)
Green status LEDs:
- Continuous:
- Off:
- Flashing:
Notes
When using B_ 5922/00_ or B_ 5922/01_ for single channel monitoring or
2-channel connection of the e-stop chain the e-stop monitor has to be
conected to the loop between S11 and S12 of the e-stop module. In this way
channel AB is monitored.
In a 2-channel e-stop loop, the e-stop monitor has to be connected to the
channel which normally is between the terminals S11 and S12 of the e-stop
module. The E-stop monitor and the e-stop module have to be connected to
the same DC 24 V power supply. When using an E-stop module with AC-
supply the minus-terminal of the e-stop monitor (A2) must be connected to
the minus-terminal of the e-stop control voltage (S21 or PE) on the e-stop
module.
Setup procedure
CANopen mode
With switch position "CANopen" the CANopen protocol is active on the
interface. The configuration of the device is made by software, e.g. Pro
CANopen. The configuration file for BH 5922 can be ordered with
reference: PN5501/CD/01/000
Plug and Play mode
With switch position "Plug and Play" a variant of the CANopen protocol
is active on the interface. The unit setting is done with a switch on the
front, see picture below. If a system is on plug and play mode it can be
switched over to CANopen protocol at any time.
Address setting Plug and Play mode
To allow the E-stop monitor to communicate with a corresponding device
via the CAN-bus the addresses have to be set with the 2 rotational
switches on the front according to the table below. Adresses between
1...49, 51...99 are possible. Adress 0 and 50 cannot be chosen in Plug
and Play mode.
E-stop monitor
BH/BL 5922 with address
1
.
.
49
Example of setting:
left switch 10
1
:
right switch 10
0
:
when all e-stop buttons are closed
when corresponding e-stop button is
pressed
when e-stop button is released,
but not acknowledged. Acknowledging
with reset button or remote reset.
output module
transmits to
IP 5503 with address
51
.
.
99
Address 14
to position 1 x 10
1
to position 4 x 10
0
Setup procedure
Notes for Plug and Play mode
On the BL-models with 2-channel monitoring of the e-stop loop 2
addressees and 2 transmission rates can be chosen (channel AB and
channel CD). For correct operation the adress settings must be different
and the transmisson rate settings must be the same.
The screen of the bus wire has to be connected to A2 of the e-stop
monitor.
Setup procedure
1.) Connect CAN-bus to terminals CAN_L and CAN_H
2.) Terminate the physical end of the bus by connecting a termination
resistor of 120 Ω between CAN_L and CAN_H on the first and last
module of the bus
3.) Connect screen of bus wire to A2
4.) Select transmission rate (e.g. 20 K bit/sec) using the rotational switch
on the front (see drawing)
5.) Select address of the module using rotational switches on the front
(see drawing and above example)
Attention:
To communicate in a system configured in Plug and Play
modus it is necessary to set one module in the system to
the address 1.
LED "ON"
LED "BUS"
switch selecting
CANopen or
Plug and Play
selection of
the transmission
rate in K bit
s
Reset button
M6316
Technical data
Input
Nominal voltage U
(A1/A2): DC 24 V
N
Voltage range:
Control voltage on S11/S12: DC 24 V
Reset input X
, X
:
1
2
BCD interface:
Output (O0,O1,O2, O3):
switched /auxiliary voltage:
Switching capacity:
Residual voltage:
BCD output, high active: (only with B_ 5922/001, B_ 5922/011)
O3 O2 O1 O0
0
0
0
0
0
0
0
1
0
0
1
0
0
0
1
1
0
1
0
0
0
1
0
1
0
1
1
0
0
1
1
1
1
0
0
0
1
1
1
1
2
setting of the unit
address with
1
ADR 10 und 10
8 status LEDs for
E-stop buttons
0,8 ... 1,1 U
N
Voltfree contact
Transistor switching +
DC 24 V
40 mA short circuit proof
typ. 0,6 V
description
input S11 without voltage
E-stop 1 active
E-stop 2 active
E-stop 3 active
E-stop 4 active
E-stop 5 active
E-stop 6 active
E-stop 7 active
E-stop 8 active
no E-stop active
0