DOLD VARIMETER IMD RN 5897/300 Monitoring Technique - Page 4
Browse online or download pdf Monitoring Technique for Measuring Instruments DOLD VARIMETER IMD RN 5897/300. DOLD VARIMETER IMD RN 5897/300 8 pages. Insulation monitor
Indicators
Connection
measuring ciruit
Indicator relay
alarm and pre-alarm
External
control input
Indicators
The operational status of the device is indicated on a 3-colour LED:
Off:
No auxiliary voltage connected
Green:
Normal operation (Insulation resistance in healthy
state)
Red:
Alarm (measured value below alarm response value)
Orange:
Warning (measured value below pre-alarm response
value)
Orange flashing: Test mode procedure (see flashing code diagramm)
Red flashing:
Failure code (see flashing code diagramm)
Flash code
orange
Status-LED
1
(measuring circuit, measuring voltage,
2
(additional control of indicator relays)
Auxiliary
voltage
Protective
conductor
M11609_b
Description
Selftest
internal tests)
Advanced Test
Error Indication
Flash code
red
Failure cause
Status-LED
Broken wire detection
1
on L(+)/L(-).
Broken wire detection
2
on PE1/PE2.
Internal failure
continously
detected in
flashing
test mode
Faulty calibration
continously
values detected in
flashing
device memory.
Notes
Risk of electrocution!
Danger to life or risk of serious injuries.
WARNING
• Disconnect the system and device from the power supply and ensure
they remain disconnected during electrical installation.
• The terminals of the control input X1-X2 have no galvanic separation to
the measuring circuit L(+) and L(-) and are electrically connected together,
therefore they have to be controlled by volt free contacts or bridge.These
contacts ore bridges must provide a sufficient separation depending on
the mains voltage on L(+)-L(-).
• Please do not connect external voltage to terminals X1/X2. The control
must only be made by bridging X1 and X2.
!
Attention!
• Before checking insulation and voltage, disconnect the monitoring device
RN 5897 from the power source!
• In one voltage system only one insulation monitor can be used. This has
to be observed when interconnecting two separate systems..
• Device terminals PE1 and PE2 must always be connected via separate
lines to different terminal points of the protective-conductor system.
• The device must not be operated without PE1/PE2 connection!
• To ensure correct measurement of the insulation resistance, there must
be a low-impedance connection (≤ 10 kΩ) or a low-impedance internal
system resistance across the source or across the load between the
measuring circuit connections L(+) and L(-).
• To ensure correct measurement of the insulation resistance, there must
be a low-impendance connection (≤ 10 kΩ) or a low-impendance internal
mains resistance across the source or across the load between the
measuring circuit connections L(+) and L(-) (or L1(+) and L2(-) when
using the ballast unit).
Attention!
nfo
• The main measuring circuit can be connected with its terminals L(+) and
L(-) both to the DC and also AC side of a mixed network; it is done most
practically where the primary incoming power supply takes place e.g.
battery networks with connected inverters on the DC side, with Generators/
Transformers with connected Rectifiers or inverters on the AC-side. To
monitor a 3NAC system the device can be connected single pole, (L(+)
and L(-) are bridged, to the neutral of the 3p4w system. The 3 phases
have a low-ohmic (approx. 3 – 5 Ohm) connection via the transformer
windings so also insulation failures of the not directly connected phases
are detected. Via the rotational switch „UN" the correct type of network
needs to be selected (see „Connection Examples").
• If a monitored AC system includes galvanically connected DC circuits (e.g.
via a rectifier), an insulation failure on the DC side can only be detected
correctly, when a current of min 10 mA can flow via the semiconductor
connections.
• If a monitored DC system includes galvanically connected AC circuits (e.g.
via an inverter), an insulation failure on the AC side can only be detected
correctly, when a current of min 10 mA can flow via the semiconductor
connections.
4
Failure recovery
Check
measuring circuit
L(+) and L (-)
Check
protective earth
connections
PE1 and PE2
Press test button again or restart
the unit by interrupting the
auxiliary supply temporarily. If the
fault remains permanent, send
device back to manufacturer for
examination.
Send device back to manufacturer
for recalobration and examination.
10.11.23 en / 800A