DOLD VARIMETER IMD RP 5898 Monitoring Technique - Page 10
Browse online or download pdf Monitoring Technique for Industrial Equipment DOLD VARIMETER IMD RP 5898. DOLD VARIMETER IMD RP 5898 12 pages. Insulation monitor
Also for DOLD VARIMETER IMD RP 5898: Translation Of The Original Instructions (8 pages), Monitoring Technique (12 pages), Translation Of The Original Instructions (17 pages)
Accessories
RP5898/61
Article number: 0066944
• Coupling device for RN 5897.12/020
• Extension of nominal voltage range U
to DC 1000 V, AC 690 V
• Weight:
• Dimensions
- Width x height x depth:
70 x 90 x 71 mm
Insulation monitor
connection
Measuring ciruit
Accessories
Flush mounting kit
Order reference: KU 4087-150/0056598
N
Approx. 110 g
M11599_a
For universal use with:
· R-series devices of
17.5 to 105 mm width
· Easy mounting
Connection Example
Ungrounded mains
3N AC 400V/230V 40...1000Hz
L1
L2
L3
N
VSG1
L(+)
L(-) VSG2
RN5897/020
X1
X2
PE1
PE2
*2)
external combined
test/reset button
PE
Ungrounded mains
RL5898: 3 AC 0...440V 40...1000Hz
RP5898: 3 AC 0...760V 40...1000Hz
L1
L2
L3
L1(+)
L2(-)
RL5898
RP5898
VSG1
L(+)
L(-)
VSG2
VSG1
L(+)
L(-)
VSG2
RN5897/020
X1
X2
PE1
PE2
*2)
External combined
test/reset button
PE
*1) Auxiliary voltage U
(A1(+)/A2) ) can also be sourced from the
H
monitored voltage system.
The voltage range of the auxiliary supply has to be taken into
account.
*2) Control input X1/X2 for external combined Test-/Reset-button with
Stop of the measuring function:
• Control 1.5 s < t < 10 s:
• Control < 1.5 s:
• Control > 10 s:
10
U N
Setting of type of network
3N AC
UH
*1)
A1(+)
A2
11
12
14
21
22
24
M11964
U N
Setting of type of network:
AC
External coupling device:
ON
UH
*1)
A1(+)
A2
11
12
14
21
22
24
M11961_a
Test function
Reset function
Stop of measuring function
12.07.21 en / 423A
: