CO2 Meter eSENSE Outdoor SE-0036 Installatiehandleiding
Connect the power after mounting.
eSENSE Outdoor
Specifications
General Performance
Compliance with ............................................... EMC directive 89/336/EEC. RoHS directive 2002/95/EG
Operating Temperature Range ........................ -22 to +115 °F
Storage Temperature Range ............................ -4 to +122 °F
Operating Humidity Range ............................... 0 to 95% RH (non-condensing)
Operating Environment ..................................... Outdoor
Warm-up Time .................................................. < 1 min. (@ full specs < 15 minutes)
Sensor Life Expectancy .................................... > 15 years
Maintenance Interval ........................................ no maintenance required
Self Diagnostics ................................................ complete function-check
Electrical
Power Input ...................................................... 24 VAC/VDC ±20%, 50 Hz (half-wave rectifier input)
Power Consumption ......................................... < 1 Watt average (Heater Off)
Connection screw terminal A ............................ 4 x 1,5 mm
OUT2)
CO
Measurement
2
Sensing method ................................................ Infrared (NDIR) waveguide technology with Automatic Baseline
Response Time (T
) ........................................ < 30 sec. @ 30 cc/min. flow rate, < 3 min. diffusion time
1/e
Repeatability ...................................................... ± 20 ppm ± 1 % of reading
3
Accuracy
.......................................................... ± 30 ppm ± 3 % of reading
3
Annual Zero Drift
............................................ < ± 10 ppm
Pressure Dependence ...................................... +1.6% of reading per kPa deviation from normal pressure 101.3kPa
Outputs
5
Output signal terminal CO
2
OUT1 linear conversion range........................... 0 - 10 VDC for 0 - 2 000 ppm
OUT2 linear conversion range ........................... 4 - 20 mA or 2 – 10VDC for 0 - 2 000 ppm
........................................................................... D/A resolution 10 bits, 10 mV
D/A conversion accuracy ................................... ± 2 % of reading ± 50 mV
Electrical characteristics .................................... R
Note 1: After long-term storage a zero calibration is recommended.
Note 2: All corrosive environments are excluded.
Note 3: Accuracy is defined after zero calibration or after minimum 23 days of continuous operation. The tolerance of the
span gas (2% unless otherwise requested) and test gas adds to the total uncertainty.
Note 4: For reference see TN-025 "on pressure sensitivity".
Note 5: The specifications are valid for the output load connected to Ground G0.
carbon dioxide transmitter Technical
1
2
for power input (G+, G0) and voltage outputs (OUT1,
Correction (ABC) and passive gas diffusion (no moving parts)
< 100 Ohm, R
OUT
.
.
> 5 kOhm (Heater Off)
LOAD
4
4