• Power + 24 VDC MAX– The RAD-0102-6 is powered from 12 to 24 Volts
DC. You may use the supplied 12 Volt DC Power Adapter or other 12 to 24
Volt DC Power Source.
• Power -
• Battery +
• Battery -
• CL01:4-20mA 4-20 mA for CO2: 0 to 50,000ppm
• GND
• CL02:4-20mA 4-20 mA for Temp: 32 to 122° F (0-50°C)
• Alarm 1 – is fixed. It cannot be configured. It is set to activate if the
average CO2 Concentration is above 0.5% (5000 ppm) for 8 hours.
• Relay 2 – is activated by Alarm 2.
• Alarm 2 can be configured to alarm when CO2 Concentration reaches
Alarm 2 Set Point.
• Alarm 2 Set Point can be configured for 0.5% (5000 ppm)
1.0%,1.5%,2.0%,2.5%,3.0%.
• Relay 3 – is activated by Alarm 3.
• Alarm 3 can be configured to alarm when CO2 Concentration reaches
Alarm 3 Set Point.
• Alarm 3 Set Point can be configured for 2.0%,2.5%,3.0%,3.5%,4.0%.
• The Peak current for all relays is 2A@30 VDC or 250 VAC.
• All relays are Single Pole Double Throw with a Common (COM), Normally
Open (NO) and Normally Closed (NC) contacts.
• All relays are Single Pole Double Throw.
• Relays are rated, 2A @ 30 VDC or 250 VAC.
Ground
Back-up battery
Back-up battery Ground
4-20mA GND