Barksdale BDS3000 Gebruiksaanwijzing - Pagina 4

Blader online of download pdf Gebruiksaanwijzing voor {categorie_naam} Barksdale BDS3000. Barksdale BDS3000 6 pagina's. Dual differential pressure switch
Ook voor Barksdale BDS3000: Gebruiksaanwijzing (6 pagina's)

Barksdale BDS3000 Gebruiksaanwijzing
7.1 Parameters
Parameter
14-segment display
SP1/SP2*
/
FH1/FH2*
/
rP1/rP2*
/
FL1/FL2*
/
EF
rES
dS1/dS2*
/
dr1/dr2*
/
Ou1/Ou2*
/
uni
OuA**
ASP**
6
Description
Hysteresis function: Switching point of solid state contact
Window function: Window High solid state contact
Hysteresis function: Hysteresis of solid state contact
Window function: Window Low solid state contact
Extended programming functions
Reset parameters to factory settings
Switching time delay – the set contact rating must be
permanently exceeded to trigger a switching function
Switching time delay – the contact rating must be
permanently lower than the set contact rating to trigger a
switching function
Switching function of solid state contact
HNO
= Hysteresis function, NO contact
HNC
= Hysteresis function, NC contact
FNO
= Window function, NO contact
FNC
= Window function, NC contact
DIA
= Diagnostic function, NO contact (only Ou2)
Select unit: bar, PSI, MPa
If the measuring range is outside the display range, unit
selection is impossible. The parameter "uni" is not
displayed.
Analog output
I
= 4... 20 mA
U
= 0... 10 V
I.INV
= 20... 4 mA
U.INV
= 10... V
Analog start value
Parameter
14-segment display
Description
AEP**
Analog end value
dPA**
Damping of analog output
ErS.A**
Error signal of analog output
Values: < 3.6 or > 22 or Off
Hi
Saved value of highest pressure measured
Lo
Saved value of lowest pressure measured
COF
Offset correction (max. 10 % of measuring range)
ddis
Damping display
Fdis
Rotate display through 180°
udiS
Unit indication
Firm
Firmware version
LocK
Locking feature
* only models with 2nd switching contact
** only models with analog output
Error list
Parameter
14-segment display
Description
sens
Sensor defect
SC1
Short circuit, solid state contact 1
SC2
Short circuit, solid state contact 2
AOut
Open output, short circuit
OL
Sensor limit positive
UL
Sensor limit negative
KEY
Internal defect
7