1.2
Pre-commissioning
The following steps inhibit automatic functions that could affect the commissioning
process and need to be carried out prior to commissioning:
Set the time and date – see 1
From the home screen, press "PROG"
Use the "+" and "-" buttons to set the programme number to 'P9' (Factory default is P9)
Press "SET"
From the home screen, press and hold "SET" and "COPY" simultaneously for 3 seconds
This action allows access to the 'Installer' programming level (opens at menu 1)
Press "COPY" twice to move to 'Menu 3' 'Bypass tEnp'
Use the "+" or "-" button to set to 'off' (OF)
This action inhibits the automatic bypass operation
Press "COPY" four times to move to 'Menu 7' 'IhuN'
Use the "+" or "-" button to set to 'off' (OF)
This action inhibits the automatic humidity controlled boost operation
Press "SET" to return to the home menu
1.3
Commissioning (see also section 4.0 Ventilation Commissioning)
Use the "+" or "-" button to set speed function to 'Boost'
From the home screen, press and hold "SET" and "COPY" simultaneously for 3 seconds
to open the installer level
Press "COPY" once to move to 'Menu 2' 'Fan 1 Low'
Press "PROG" once to 'Fan 1 Boost' (Extract/Exhaust fan)
Use the "+" or "-" button to set the desired speed (Factory default speed is 50%)
Note: The installer level access will time out after 1 minute of inactivity but will record any
changes made to the settings
Press "SET" to record the settings and return to the home screen
Press "ESC" to discard the settings and return to the home screen