EKHO EK-WL8-OV/AU Snelstarthandleiding - Pagina 5

Blader online of download pdf Snelstarthandleiding voor {categorie_naam} EKHO EK-WL8-OV/AU. EKHO EK-WL8-OV/AU 9 pagina's. Wireless optical smoke detector with build-in voice annunciator and visual alarm device

EK-WL8-OV/AU
WIRELESS OPTICAL SMOKE
DETECTOR
WITH BUILD-IN VOICE ANNUNCIATOR
AND VISUAL ALARM DEVICE
STFV.425238.037-AU-UM rev. 23
20.08.2020
Page 5 from 9
SYNCHRONIZATION
To indicate the direction of evacuation in the corridors the devices can be combined
into a dynamic evacuation system. In this mode devices are installed one after
another (maximum 16 pcs.). When system gets an activation command from control
panel, the devices start reproducing speech (sound) information, and then, one after
another, sequentially reproduce a short multi-frequency signal together with a light
flash. The traveling light-sound "wave", created in this way, indicates the direction to
a safe escape route.
NOTE After programming or power on the devices or translator it takes about 10
minutes to finish the synchronization.
Sound synchronization with other devices in the system is not worse than 50ms.
TESTING
A test alarm can be activated with a magnet by
holding it for 1 second near the area on the
opposite side of the marks on the detector's
base.

ANALOG DATA

The device provides the translator module with
analog data about the current smoke level, air
temperature, dust in the chamber as well as voltage levels on its batteries. This
information can be viewed in the "Streletz-Wizard" software.
By analyzing the voltage or dust levels, you can manage your maintenance
procedures and predict when you will have to replace the batteries or clean the
smoke detectors. Please refer to the software manual for full instructions on how to
use the program for system maintenance.
5