232i Wiring Diagrams
The diagram above shows how to connect two keypads to control a single door. Entering your code on keypad 2 unlocks the
maglock directly. When you enter your code on keypad 1, it triggers the REX input of keypad 2, which unlocks the door.
When using a propped door or forced door alarms, connect the alarms to keypad 2. Also use keypad 2 to shunt out an existing
alarm system with the alarm shunt relay.
Please note that user codes must be programmed into both keypads.
6-040401 X2
The diagram to the left shows how to control
the keypad LED's using an external alarm
panel. To access the keypad's main circuit
board, remove the relay board.
To control the LED's externally cut the four
traces in the box underneath connector J1.
Before connecting the alarm panel's LED
control lines to J1 verify the traces are cut.
To verify, measure continuity between the
end of the wire on the wire harness and the
square pad on the circuit board below the box
corresponding to the wire you're measuring.
Permanent damage to the keypad may
result if voltage is connected to J1 when
the traces are not cut.
3