Advance Appliances EG6-U Installatie- en gebruikershandleiding - Pagina 3

Blader online of download pdf Installatie- en gebruikershandleiding voor {categorie_naam} Advance Appliances EG6-U. Advance Appliances EG6-U 12 pagina's. Electric boiler 6, 9 & 12kw

Advance Appliances EG6-U Installatie- en gebruikershandleiding
OPTIONAL SEALED SYSTEM KIT AA 0400
KIT INCLUDES:
COLD FILL HOUSE WITH DOUBLE ISOLATION
3 BAR PRESSURE RELIEF VALVE 1/2"
EXPANSION VESSEL 8 LITRES
PRESSURE GAUGE

TECHNICAL SPECIFICATIONS

POWER RATING
FLOW AND RETURN
ELECTRICAL SUPPLY
PROTECTION
PUMP
PUMP SETTING
OUTPUT TEMP (MAX)
UNDERFLOOR UNITS
OUTPUT TEMP (MAX)
HIGH LIMIT TEMP
CONTROL 2 STAGE
NOM HEAT OUTPUT
AUTO AIR VENT
FLOW SWITCH
AUTO BY PASS
MIN PRESSURE COLD FILL 0.6 BAR
MAX PRESSURE HOT
HEAT EXCHANGERS
IPX RATING
6kW
22MM BOTTOM ENTRY
SP 240 VAC 50hz 30A
32 AMPS
15/50
AUTO
80°C
60°C
90°/95°C
20,000 BTU
FITTED
FITTED
FITTED
3 BAR
STAINLESS STEEL
3Kw PODS x 2
1
9kW
22MM BOTTOM ENTRY 22MM BOTTOM ENTRY
SP 240 VAC 50hz 40A
45 AMPS
15/50
AUTO
80°C
60°C
90°/95°C
30,000 BTU
FITTED
FITTED
FITTED
0.6 BAR
3 BAR
STAINLESS STEEL
3Kw PODS x 3
1
3
12kW
SP 240 VAC 50hz 50A
63 AMPS
15/50
AUTO
80°C
60°C
90°/95°C
40,000 BTU
FITTED
FITTED
FITTED
0.6 BAR
3 BAR
STAINLESS STEEL
3Kw PODS x 4
1