DOTECH FX7SE-16P-R4 Gebruikershandleiding
Blader online of download pdf Gebruikershandleiding voor {categorie_naam} DOTECH FX7SE-16P-R4. DOTECH FX7SE-16P-R4 3 pagina's. Compact digital thermostat
Compact Digital Thermostat
FX7SE series
User Manual
1. Overview
: Basic Specification
List
Dimensions
79.5(W)mm X 36(H)mm X 39.7(D)mm
Power
200 - 230 Vac, 50/60 Hz
Consumption
MAX 6 VA
Connection
Screw Bolt Connector, wire range : 24~12 AWG
Input
Temp. Sensor Input 1point
Output
Relay Output 1point (250 Vac / 16 A or 5 A)
Operation
Temp.: – 10 ~ 60°C, Humidity: Below 90 %RH
Storage
Temp.: – 20 ~ 70°C, Humidity: Below 90 %RH
※ Specifications are subject to change without prior notice.
: Components
20max.
20max.
Product
EPOXY(Black)
: Accessories
EPOXY(Black)
20max.
35
EPOXY(Black)
Ø5
35
SUS PIPE
Ø5
SUS PIPE
35
100
Ø5
Ø6
SUS PIPE
SUS PIPE
100
Ø6
SUS PIPE
ZH2014-11003
DOTECH inc.
6F, JOONGANG-ILBO B/D, 30, Dongsan-ro,
Danwon-gu, Ansan-si, Gyeonggi-do, KOREA
Tel : 82-31-495-3767, Fax : 82-31-495-3917
www.dotech21.com
Description
LEAD WIRE(2m)
LEAD WIRE(2m)
LEAD WIRE(2m)
SHRINK TUBE
LEAD WIRE
SHRINK TUBE
LEAD WIRE
SHRINK TUBE
LEAD WIRE
SPRING PROTECT
LEAD WIRE
SPRING PROTECT
LEAD WIRE
※ Pre Cautions for Use
1. This Product may cause an Electric Shock in handling, please do not attempt to open it with power turned on.
2. This Product should be install in a place fixed securely by a rack or panel.
3. This Product can be use under the following environmental conditions.
① Indoor ② Pollution Degree 2 ③ At an Altitude of 2000m or below
4. Power input must be within the designated ranges.
5. To turn on or turn off power supply for this product, please the circuit breaker or switch of a standard product of IEC 60947-1 or IEC
60947-3 product and install it within a close distance allowing convenient operation by user.
6. Please be understood that if this product is dismantled or modified discretionary, after sales service will not be able to be provided.
7. An output wire to be used for this product should be inflammable grade FV1 (V-1 grade or above), the thickness of the wire should
be AWG No. 20 or above(0.50mm2).
8. In order to prevent it from an inductive noise, please maintain the high-voltage wire and power wire separated.
9. Please avoid installing the product in a place where a strong magnetism, noise, severe vibration and impact exist.
10. When extending the sensor wire, use a shield wire and do not extend it unnecessary long.
11. The sensor wire and signal wire should be away from the power and load wires using conduits separately installed.
12. Please avoid using the product near a device generating strong high frequency noise (high-frequency welding machine,
high-frequency sewing machine, high-frequency radiotelegraph, high capacity SCR controller)
13. Product's damages other than those decribed in the guarantee conditions provided by the manufacturer shall not be respoinsible
by us.
14. If this unit is used to control machineries (Medical equipment, vehicle, train, airplane, combustion apparatus, entertainment,
processing and transportation equipment, elevator and various safety device etc.) enabling to effect on human or property, it is
required to install fail-safe device.
※ The Aforementioned precautions must be observed, and if you fail to do so, it may cause a product's breakdown.
※ The specifications, dimensions, and etc. are subject to change for enhancement without a prior notice.
※ Special feature
- Inside the desired temperaturetable
- Sensor error detection, Sensor calibration
- Water proof front(IP65)
- Compact size(34mm)
- RS485
- Select temperature unit (°C, ℉)
: Order Information
Model
FX7SE-16P-00
FX7SE-16P-R4
FX7SE-05P-00
FX7SE-05P-R4
Bracket 2ea
DPR-TH01-AT5-2M : NTC 5KΩ at 25°C / -50~105°C / ±0.3°C at 25°C
DPR-TH01-ET-2M : NTC 5 KΩ at 25 °C / -50~105°C / ±0.3°C at 25°C
DPR-TH02-P6D100L : NTC 10 KΩ at 25 °C / -50~150°C / ±1.5°C at 25°C
- 1 -
Description
Basic Model, Relay Output 16A
RS485 Comm. Model, Relay Output 16A
Basic Model, Relay Output 5A
RS485 Comm. Model, Relay Output 5A