Baumer AMG11 N13 Handmatig - Pagina 10
Blader online of download pdf Handmatig voor {categorie_naam} Baumer AMG11 N13. Baumer AMG11 N13 41 pagina's. Absolute encoders with profinet interface
4.2. Inserting of the Encoder into the Project
Use the mouse to drag base module „GxxMW" from the hardware catalog at right to the bus rail.
Use the mouse again to drag encoder I/O module e.g. "Encoder data 32 bit EA + 32 bit" from the right out of
the hardware catalog to plug-in position 1 of the module window at left below in the hardware catalog.
4.3. Assigning the device name
Device identification in the network requires the worldwide unique MAC device address, the (statically or
dynamically assigned) IP address, and third a unique device name in the PROFINET network. All three
identifiers are used when booting the system. The project work only requires assigning the device name.
4.3.1.
Setting the Device Name in the Project
Double-click on the encoder symbol in HW-Config window. The properties window opens with an input field to
enter the desired device name.
4.3.2.
Automatic Name Assignment
The encoder's device name can also be set automatically.
When shipped (or after a factory setup), the device name is clear ("").
Preconditions for automatic name assignment:
•
cleared device name
•
active option „Support device replacement without exchangeable medium" in the properties window
of the PLC – PN-IO – General (see screenshot below)
•
topology planning.
Automatic name assignment runs as soon as the installed encoder is accessed in the network.
Baumer_BUDE-PROFINET_MA_EN.docx
14.06.2016 / bja
10/41
www.baumer.com