Baumer Hubner Berlin microGen PMG10 Bedieningshandleiding - Pagina 26

Blader online of download pdf Bedieningshandleiding voor {categorie_naam} Baumer Hubner Berlin microGen PMG10. Baumer Hubner Berlin microGen PMG10 44 pagina's. Absolute encoder
Ook voor Baumer Hubner Berlin microGen PMG10: Bedieningshandleiding (40 pagina's), Bedieningshandleiding (40 pagina's)

6
|
Electrical installation
6.1.4

DeviceNet terminal box

1
2
3
Ill. 13: DeviceNet Terminal box
1
Setting the terminating resistors
3
Setting the user address
Pin assignment
DRAIN
GND
UB
CAN_H
CAN_L
INFO
Connectors with the same designation are internally connected and identical in functionality.
These internal terminal connections UB-UB / GND-GND may be loaded with max. 1 A each.
6.1.5

Setting the terminating resistor

ON = final bus user
OFF = any bus user
6.1.6

Setting the bus user address

1. Digit user address
2. Digit user address
(Illustration shows example user address 23).
26
Shield connection
Ground connection for UB
Operating voltage 10-30 V DC
CAN Bus Signal (dominant HIGH)
CAN Bus Signal (dominant LOW)
Operating Manual
2
Setting the transmission rate
PMG10 & PMG10P DeviceNet | V1
Baumer Hübner