Douglas Lighting Controls WORXID1-N-N Installatiehandleiding

Blader online of download pdf Installatiehandleiding voor {categorie_naam} Douglas Lighting Controls WORXID1-N-N. Douglas Lighting Controls WORXID1-N-N 2 pagina's. Diversa occupancy & vacancy sensors - recessed ceiling, passive infrared (pir), 24vac

Installation Guide
PART NO.
FEATURES
WORSID1-N-N
• Commercial grade components for long term reliability
standard lens, PIR, 24Vac,
1-pole
• Straightforward wiring for quick installation
WORXID1-N-N
extended lens, PIR, 24Vac,
• Factory configured for the most common applications
1-pole
WORSID2-DPR-L
• DIP switches and dials for advanced functionality
standard lens, PIR, 24Vac,
2-pole, dimming, photo,
• Options:
relay, low temp.
WORXID2-DPR-L
Standard, Extended, High-Bay Lens
extended lens, PIR, 24Vac,
Dimming, Photo Sensor, Isolated Relay
2-pole, dimming, photo,
Low Temperature/High Humidity
relay, low temp.
WORBID2-DPR-L
high-bay lens, PIR, 24Vac,
2-pole, dimming, photo,
relay, low temp.
Operation
Diversa 24Vac (low voltage) sensors are powered by 24Vac from either the Diversa Series Power Pack (WP-PP20-***)
or a 24Vac transformer. When in operation, the sensor will detect initial motion using PIR; once motion is detected,
the sensor and Power Pack (or connected diode pulse relays) contacts will close. Motion through Passive Infrared
(PIR) is used to maintain the occupied condition as long as occupants remain within coverage pattern of Sensor.
Sensor Location Guidelines
To optimize the performance of Diversa Sensors, please review the coverage pattern, range, and model to
match with the application. Room dynamics will change when people and furniture are occupying the space.
In some rooms, after move in, some sensors may require adjustments.
• Ensure that the sensor is at least 30 inches away from air handlers/registers and not pointed directly at
windows
• Check that you are installing the right product (check the product model number) as per the drawings
Sensor Location Guidelines for "P" models
• Place outside the direct cone of light from fixtures
• Between 3 to 12 feet from windows
• As close as possible to the fixture being controlled
• Above the least illuminated space in the work area
• Away from lighting that is not being controlled by the sensor
SPECIFICATIONS
Power
±
• 24Vac
25%
• Class 2 low voltage source
• 60Hz
• Use #18AWG wire
Outputs
• Diode Pulse: Each output is capable of driving up to four Diode
Pulse relays
• 0-10V Dimming: Connections are polarity-sensitive - up to 25mA
sinking
• Isolated Relay: SPDT Form C contact rated for 1A at 30Vdc
Power Consumption
• 9.5mA Standard
• 14.0mA with Auxiliary Relay
Approvals
• FCC
Environment
• Indoors, stationary, non-vibrating, non-corrosive atmosphere and
non-condensing humidity
• Ambient Operating Temperature: 32°F to 104°F (0°C to 40°C)
• Storage Temperature: -14°F to 140°F (-25°C to 60°C)
Diversa by Douglas Lighting Controls
Diversa Occupancy & Vacancy Sensors - Recessed Ceiling, Passive Infrared (PIR), 24Vac
Line Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor
(Shown with cover
plate removed)
Light Level Dial
Used to determine light
level for Photo Functions
Grey (-)
0-10V Dimming
(Only models with Dimming)
Wiring
Instructions
The WOR Series Low Voltage sensors are equipped with #22AWG Leads. Use appropriate sized wire nuts to
connect the wires to the incoming load terminations.
Wiring to a Power Pack
(2-pole sensor requires 2-pole Power Pack)
DIMENSIONS/MOUNTING inches (mm)
Unit attaches to mounting ring with
screws or it can be mounted into an
octogan box.
Ceiling tile
Mounting
0.88"
Wire
(2 2 )
ring
2.0"
(52)
4.17"
3 0 ° Tilt
(106)
DIPs and Dials
under cover
plate
The WOR sensor will fit an octagon
box. It is very important that conduits
be attached at opposite ends of the
box.
Conduit
Octagon Box
Use a 2 1/8 " or more, deep box.
If the box is less, use the spacer ring.
DIP Switches
Manual Override Button
Test Mode LED
Time Delay Dial
Ranges from 30s to 30 min.
Full turn Clockwise for Auto Time
Full turn Counterclockwise for Test Mode
Auto Time LED
Violet (+)
Blue
Return
Red
Orange
Primary Output Pole
Red/White
Yellow/White
Yellow
Yellow/Black
Sensor Link
NC
COM
NO
Secondary Output Pole
WP-PP20-D
Black
White
Black
Black
White
White
Red
Red
Orange
Orange
Sensor
Link
Sw
Sw
Override / Multi-Level Switching
www.douglaslightingcontrols.com
Installation
Standard Lens (S)
• Locate the sensor near the entrance door wall to prevent it from viewing out into the hallway.
• The lens can tilt, allowing the sensor to be pointed toward the area in front of the entrance door.
• Positioning the sensor in this manner ensures that an occupant moves across the longest detection beam
upon entrance, utilizing the sensor's maximum PIR range.
• Designed for a mounting height of 7-15 ft
White
24Vac
Typical Enclosed O ce
Extended Lens for Larger Rooms (X)
• Place the sensor near the center of the room ceiling. Locate it so the approximate distance of 27ft in
or in dead center of room.
• Tilt the lens to aim the detection zone to the bottom of the door.
• Positioning the sensor in this manner ensures that the beam does not reach outside the room without
reducing sensitivity.
• Optimal usage is to detect large motions such as walking.
• Designed for a mounting height of 7-15ft.
27ft
C
27ft
Typical Classroom
High Bay Lens for High Ceiling Applications (B)
• For 15 to 40 foot ceilings
• Position sensor based on ceiling height, beam pattern
and coveage requirements
14040200-C
Top View
14 ft
7 ft
0 ft
7 ft
14 ft
Side View
9 ft
0 ft
14 '
12 ' 10 '
6 '
3 '
0 '
3 '
6 '
10 '
12 '
14 '
Top View
27 ft
14 ft
0 ft
14 ft
27 ft
Side View
9 ft
0 ft
27 '
16 '
9 '
3 '
0 '
3 '
9 '
16 '
27 '
Top View
40 ft
18 ft
0 ft
18 ft
Side View
40 ft
40 ft
20 ft
10 ft
0 ft
40 '
30 '
20 '
10 '
0 '
10 '
20 '
30 '
40 '