Advanced MxPro4 Series Handmatig - Pagina 4

Blader online of download pdf Handmatig voor {categorie_naam} Advanced MxPro4 Series. Advanced MxPro4 Series 6 pagina's. Sounder booster
Ook voor Advanced MxPro4 Series: Installatieblad en beknopte referentiehandleiding (4 pagina's), Handmatig (12 pagina's)

Advanced MxPro4 Series Handmatig

2 Fault Indication

Any open circuit condition between the 'FAULT I/P' terminals will result in the panel indicating a 'Sounder Open
Circuit' fault. When the 'FAULT I/P' terminals are connected to the PSU's 'Fault' relay, the panel will indicate a
'Sounder Open Circuit' fault should the PSU develop any fault.
Normal sounder circuit open circuit and short circuit monitoring is applicable on the boosted sounder output
circuit.
4
www.advancedco.com