2 Fault Indication
Any open circuit condition between the 'FAULT I/P' terminals will result in the panel indicating a 'Sounder Open
Circuit' fault. When the 'FAULT I/P' terminals are connected to the PSU's 'Fault' relay, the panel will indicate a
'Sounder Open Circuit' fault should the PSU develop any fault.
Normal sounder circuit open circuit and short circuit monitoring is applicable on the boosted sounder output
circuit.