Advanced Air 26SCD Installatie-, Bedienings- en Onderhoudshandleiding - Pagina 5

Blader online of download pdf Installatie-, Bedienings- en Onderhoudshandleiding voor {categorie_naam} Advanced Air 26SCD. Advanced Air 26SCD 13 pagina's.

SMOKE CONTROL – 26SCD ADJUSTABLE FRAME SYSTEM FOR TWO HOUR RIGID SUPPORTING CONSTRUCTION (SUPPORT ONE SIDE)
M10 drop rods
AFS rail
Fire batt
AFS bracket,
bracket slot,
and Z-piece
Access door
122mm thick, two hour rated rigid
supporting blockwork, masonry
or homogenous concrete wall
to BS EN 1363-1:2020
26SCD
PRODUCT
EFR-20-002148 REV1 RC
CLASSIFICATION REPORT NO.
TESTED INSTALLATION METHOD SHOWN. DIFFERING INSTALLATION METHODS TO THIS MUST BE APPROVED BY THE BUILDING CONTROL AUTHORITY (BCA) BEFORE PROCEEDING.
RIGID SUPPORTING CONSTRUCTION W/AFS
APPLICATION
E120 (Vew i  o) S500 C 10000 AA multi • E120 (Vew i  o) S500 C mod AA multi
CLASSIFICATION
Preparation
1
Ensure that the damper is kept
in a clean dry environment and
200mm x 200mm
that there is no damage to the
damper.
2
Remove
all
the
packaging
200mm x 200mm
before installation.
3
Work out the opening size to be
cut using the adjacent table.
Installation sequence
4
Two M10 drop rods shall be fitted on the side of the drywall to which the access side of the damper
will be positioned. These should be securely installed in line with the manufacturer's fixing instructions
in a position to match the AFS rail.
5
The drop rods should have a nut screwed on for clamping the rail from above.
6
Slide the AFS rails on each side of the damper into the brackets and insert the "Z" piece into the
bracket slot pushing it up against the underside of the rail. Insert the 8mm bolt from above into the slot
through the "Z" piece fitting the nut until tight to secure the rail.
7
The damper should be mounted centrally in the opening with the access side flush with the wall, as
detailed in the drawing. The drop rods are to slide through the slots in the rail and a nut screwed on
to take the support of the damper rail. The damper must then be levelled and when in the correct
position the nut above the rail should be tightened against the rail.
8
The galvanised mild steel ductwork connecting to the damper spigots must overlap by up to 40mm,
leaving a minimum 10mm clearance for any duct expansion in a fire situation.
9
The galvanised mild steel ductwork connections must be sealed with an approved galvanised mild
steel ductwork sealer.
10
The connecting galvanised mild steel ductwork must be independently supported within one metre of
the connections and have been installed in accordance with DW144.
11
The gap between the damper and the wall opening will need filling with two layers of 50mm thick
140kg/m3 fire batt cut to an interference fit and pushed in to place. All cut edges must be sealed with
a fire batt sealant to BS EN 13501-2. A fire rated intumescent mastic to BS EN 13501-2 shall be applied
to each joint.
12
An access door should be fitted on the access side of the damper for inspection and maintenance of
the damper.
13
When the damper installation has been completed checks should be made to ensure the AFS rails are
secure and there is no movement, operation of the damper should be checked.
14
Complete DW145 Fire Damper Checklist.
Nom. duct size
Width
Opening
Opening
Opening
min.
max.
min.
Nom. duct
Nom. duct.
Nom. duct
and above
+194mm
+350mm
+100mm
Below
394mm
550mm
300mm
Circular duct
Nom. duct
Nom. dia.
Nom. dia.
over 175mm
+219mm
+550mm
+125mm
Circular duct
394mm
550mm
300mm
under 175mm
Height
Opening
max.
Nom. duct
+350mm
550mm
Nom. dia.
+375mm
550mm
5