Amprobe TIC 300 PRO Gebruikershandleiding - Pagina 9
Blader online of download pdf Gebruikershandleiding voor {categorie_naam} Amprobe TIC 300 PRO. Amprobe TIC 300 PRO 15 pagina's. Meet the new standard in non-contact, high voltage detection
Ook voor Amprobe TIC 300 PRO: Gebruikershandleiding (18 pagina's), Snelstarthandleiding (4 pagina's)
Find Quality Products Online at:
OPERATION
ON/OFF Button
When the TIC 300 PRO is activated, the blue LEDs and
beeper will pulse at a slow rate about twice a second.
The red LED of the range (HIGH) will turn ON.
TEST Button
The TEST button should be used prior to testing actual
power circuits. The TEST function will cause the blue
LEDs and beeper of the range selected (LOW or HIGH) to
pulse at a fast rate.
OSHA listed clearance distances for working with
voltage. National or local requirements may be
different.
Line voltage (kV)
Phase to ground
phase to phase
(ft-in)
(m)
0.03 to 1.0
Note1
Note1
1.1 to 15.0
2-1
0.64
15.1 to 36.0
2-4
0.72
36.1 to 46.0
2-7
0.77
46.1 to 72.5
3-0
0.90
72.6 to 121
3-2
0.95
Note1 – No contact necessary
�Caution: If a three phase circuit is being checked and
one phase is open, the voltage from another phase
maybe detected and will give a faulty indication. Always
make sure that the phase cables are separated by at least
20 in (50.8 cm).
5
GlobalTestSupply
www.
Phase to phase
(ft-in)
(m)
Note1
Note1
2-2
0.66
2-7
0.77
2-10
0.77
3-6
1.05
4-3
1.29
.com