COMECO TC67U Bedieningshandleiding

Blader online of download pdf Bedieningshandleiding voor {categorie_naam} COMECO TC67U. COMECO TC67U 4 pagina's. Programmable process indicator
Ook voor COMECO TC67U: Bedieningshandleiding (17 pagina's)

Specifications
Input
Outputs:
Electromechanical relay
SSR
MOS gate
Output for external SSR
- REL1
- REL2
Serial Interface
Power Supply
Auxiliary Supply Output
Consumption
Measurement Error
Temperature Drift
RTD Line Error
Cold-junction Error
Operating Temperature / Humidity
Protection Class: front / terminals
Warranty and Support
...............................
serial number
...............................
manufacturing date
QC check mark .............(passed)
(stamp)
88 Slavyanska Str.
P.O.Box 378
Plovdiv 4000, BULGARIA
tel: +359 32 646523, 646524
fax: +359 32 634089, 646517
QD-8.2.4-WC
Wiring
Important notes:
Strictly observe
the requirements for
RS485 network building!
With DC power supply,
the polarity
does not matter.
In case of 90...250 VAC/DC
power supply,
grounding the device
through terminal 2
is mandatory for covering
safety standards.
programmable
up to 2
5A/250VAC with NO/NC contact
1A/250VAC
0.1A/60V, optically isolated
5...24 VDC, 30 mA
relay,
SSR,
MOS gate,
for ext. SSR
relay,
SSR,
MOS gate,
for ext. SSR
RS485, isolated,
RS485 for "PolyMonitor", isolated
230 VAC,
90...250 VAC/DC,
24 VDC,
12...24 VAC/DC,
.............................................
≤ U
(DC); ≤1.2*U
(AC),
24 VDC, 30 mA
p
p
less than 3 VA
≤ ± 0.3% from span
≤ 0.02% from span for 1 °C
≤ ± 0.001%/Ω at R
≤ 50 Ω
lin
.
≤ ± 1 °C at air temperature -10...80 °C
-10...65 °C / 0...85% RH
IP54 / IP20
Warranty
COMECO warrants this product
to be free from defects in materials
and workmanship for 2 years. If your unit
is found to be defective within that time,
we will promptly repair or replace it.
This warranty does not cover accidental
damage, wear or tear, or consequential
or incidental loss. This warranty
does not cover any defects caused
by wrong transportation, storage, installation,
or operating (see 'Specifications').
Technical support
In the unlikely event that you encounter
a problem with your COMECO device,
please call your local dealer or contact
directly our support team.
Input signal wiring
Connect the input
with regard to its type
through the respective terminals
on the device back.
3-wire voltage transmitters must
be supplied externally!
Output wiring
Connect the outputs
with regard to their types
(see 'Specifications')
via the respective terminals.
RS485 wiring
Connect the unit
to RS485 network line
via the respective terminals.
Power supply wiring
Connect the right power
supply voltage for your device
(see 'Specifications').
More detailed
wiring diagrams are available at
comecogroup.com under
'Support' tab.
16
COMECO Inc., P.O.Box 378, Plovdiv 4000, BULGARIA, tel: +359 32 646523, 646524, fax: 634089
e-mail: [email protected], WWW.COMECOGROUP.COM
PROGRAMMABLE PROCESS INDICATOR
Please read this Operation Manual before mounting and operating!
Communication Protocol
4
Parameter Symbol
Input Type
inp
Unit
unit
Point Position
pnt
Input Low
i.hi
Input High
i.lo
Input Correction i.cor -199...999
Address
addr
Baud Rate
baud
Gradient
grad
Filter Time
f.t
Filter Band
f.b
Input Value
p.v
Error Info
error **
* Input Value (read-only)
numerical value with ISU - measured input value
sat.lo - ADC under-range
sat.hi - ADC over-range
inp.br - sensor break
break - device failure
noise - noisy measurement
** Error Info
0 - initializes non-volatile memory
-1 - error FAL (read-only)
1...29 - errors W01... W29 (read-only)
TC67U
O PERA T ION MANUAL
Save the Manual for future references!
Table 2
Protocol architecture
The protocol is based
Value
on UART protocol with:
pt100, pt1000,
ptc1, ptc2,
r.0.1k,
t.c.b, t.c.j,
t.c.k, t.c.r,
t.c.s, t.c.t,
ASCII protocol is used
u, u.0.10,
for communicating,
i.0.20, i.4.20
and the information
is exchanged in frames.
c, f
Each frame consists of 1,
0, 1, 2
or 2 words separated
-199...999
by byte 32 (SPACE),
-199...999
and ends with bytes 13 (CR)
and 10 (LF). The first word
in the frame denotes
1...254
a parameter 'Symbol'
1200, 2400,
as taken from Table 2 and
4800, 9600
the second word (if needed)
0...999
is the parameter 'Value',
both spelled with only
0...999
small Latin letters, digits,
0...M
dots, and/or the '-' sign.
*
Device activating
To respond to commands,
the device should be active.
For a device to be activated,
it must receive a
command, where 'х' is
the value of the parameter
Address or the value '255' (if
device address is unknown),
and respond to it with ok..
If a device does not respond
even to
the UART protocol settings,
chiefly Baud Rate value.
13
Baud Rate - as defined
by parameter Baud Rate;
Data bits - 8;
Parity Control - Even;
Stop bit - 1.
U
х
U
255, check