Setting the COM Port Baud Rate
Each BSU IIs baud rate must match the NetGuardian baud rate setting. The baud rate is defined by setting DIP
switches 5-7 — see Figure 7.2 and Table 7.C for DIP switch baud rate definitions.
Note: The required baud rate for NetGuardian interface is 1200.
8
Configure the NetGuardian
The NetGuardian must be provisioned to operate the BSU II. You'll need to specify the number of BSU IIs on the
communication bus, the data port baud rate, and Sound On Timer duration. Use the following sections to
provision the NetGuardian via NGEdit or the Web Browser Interface.
8.1
Using NGEdit
Note: NetGuardian Firmware 3.0H and above required to configure the BSU II. 4-wire 485 mode is enabled
automatically at 1200 baud. The supported communication rate for BSU II applications is 1200 baud.
1. From the main screen select the Ports tab.
Fig. 7.2 The BSU II set to Address 2, baud rate 9600.
DIP Switch
000
100
010
110
001
Table 7.C DIP switch baud rate definitions.
Fig. 8.1 Configure BSU II support in NGEdit > Ports Tab.
Definition
1200
2400
4800
9600
19200