AirStage ABUA14RLAV Installatiehandleiding - Pagina 8
Blader online of download pdf Installatiehandleiding voor {categorie_naam} AirStage ABUA14RLAV. AirStage ABUA14RLAV 17 pagina's. Indoor unit (floor / ceiling type)
Ook voor AirStage ABUA14RLAV: Bedieningshandleiding (8 pagina's)
5. INSTALLING DRAIN HOSE
]
Install the drain hose in accordance with the instructions in this Installation Manual
and keep the area warm enough to prevent condensation. Problems with the piping
may lead to water leaks.
Use general hard polyvinyl chloride pipe and connect it with adhesive (polyvinyl chloride)
so that there is no leakage.
Always heat insulate the indoor side of the drain hose.
Use a drain pipe that matches the size of the drain hose.
• Do not perform a rise, trap and air bleeding.
• Provide a downward gradient (1/100 or more).
• Provide supporters when long pipes are installed.
• Use an insulation material as needed, to prevent the pipes from freezing.
• Install the pipes in a way that allows for the removal of the control box.
Drain pipe
When using the drain port on the left side of the unit, remove the drain cap and install it to
the right side drain port.
(Only when suspended from the ceiling)
Unit
INSTALL THE DRAIN HOSE
Working procedure
1)
Install the attached drain hose to the drain port of the body. Install the hose band
from the top of the hose within the graphic display area. Secure fi rmly with the hose
band.
2)
Use vinyl adhesive agent to glue the drain piping (PVC pipe) / [Φ 3/4 in. (19 mm) I.D.
Φ 1-1/16 in. (27 mm) O.D.] which is prepared on site or piping socket. (Apply color
adhesive agent evenly until the gauge line and seal)
3)
Check the drainage.
4)
Install the heat insulation.
5)
Use the attached heat insulation to insulate the drain port and band parts of the body.
Top view
13/32 to 19/32 in. (10 to 15 mm)
Drain hose
(Accessories)
Side view
Applying
area of
Hard PVC side
adhesive
5/32 in. (4 mm) or less
Wrap the Drain hose insulation around the drain hose connection.
Top view
3-15/16 in.
(100mm)
Drain hose
En-7
CAUTION
Pipe size
Φ 3/4 in. (19 mm) [I.D.],
Φ 1-1/16 in. (27 mm) [O.D.]
Drain cap
Drain pan
Ensure there is no space
Hose Band
(Accessories)
Soft PVC side
Joint pipe
(Field supply)
Drain pipe (Field supply)
Φ 3/4 in. (19 mm) [I.D.], Φ 1-1/16 in. (27 mm) [O.D.]
Drain pan
Drain hose insulation
(Accessories)
Hose opening view
Wind the attached heat insulation
around the hose band. Make sure
the alignment is on top.
A. Floor console type
Be sure to arrange the drain hose so that it is leveled lower than the drain hose connect-
ing port of the indoor unit.
GOOD
Arrange the drain
hose lower than
this portion.
Do not install the unit so that the drain hose side is too high. Height A should be less
than 3/16 in. (5 mm).
Prohibited
B. Under ceiling type
Be sure to arrange the drain hose so that it is leveled lower than the drain hose connect-
ing port of the indoor unit.
Arrange the drain hose
lower than this portion.
GOOD
When drain hose is arranged backward.
Secure the drain hose with the VT wire.
VT wire
hole
Pass the drain hose
Cut the grille
through here.
6. ELECTRICAL WIRING
]
Electrical work must be performed in accordance with this Manual by a person
certifi ed under the national or regional regulations. Be sure to use a dedicated circuit
for the unit.
An insuffi cient power supply circuit or improperly performed electrical work can cause
serious accidents such as electric shock or fi re.
Before starting work, check that power is not being supplied to the indoor unit and
outdoor unit.
Use the included connection cables and power cables or ones specifi ed by the
manufacturer. Improper connections, insuffi cient insulation, or exceeding the allowable
current can cause electric shock or fi re.
Prohibited
Prohibited
Drain hose
CAUTION
Drain hose
Prohibited
Drain
hose
Prohibited
VT wire
Base (Bottom)
Intake grille
Drain hose
WARNING