6.2. Wiring method
EXAMPLE
Outdoor unit or RB unit *1
Transmission
Indoor unit
Transmission
Remote
control
Power supply
*2
Breaker
Power supply
Remote controller
(Master)
*1: When connecting to the Heat Recovery System, refer to the installation manual
of the RB unit.
*2: Earth (Ground) the remote controller if it has an earth (ground) cable.
*3: When connecting the 2-wire type remote controller, Y3 is not used.
(Crossover wiring of power supply)
Indoor unit
Power supply
Pull box
Breaker
Power supply
* Earth (Ground) the remote controller if it has an earth (ground) wire.
] 1
6.3. Unit wiring
• Before attaching the cable to terminal block.
6.3.1. Power supply cable
25 mm
Earth
35 mm
(ground) cable
A. For solid core wiring
(1) To connect the electrical terminal, follow the below diagram and connect after looping
it around the end of the cable.
(2) Use the specifi ed cables, connect them securely, and fasten them so that there is no
stress placed on the terminals.
(3) Use an appropriate screwdriver to tighten the terminal screws.
Do not use a screwdriver that is too small, otherwise, the screw heads may be dam-
aged and prevent the screws from being properly tightened.
(4) Do not tighten the terminal screws too much, otherwise, the screws may break.
(5) See the table for the terminal screw tightening torques.
(6) Please do not fi x 2 power supply cables with 1 screw.
Strip 25 mm
Screw with
special washer
Cable
Cable end (Loop)
Terminal block
En-7
Indoor unit
Remote
control
*2
*2
*3
*3
Breaker
Breaker
Remote controller
(Slave)
Indoor unit
Power supply
Power supply
Pull box
Screw with
special washer
Cable end (Loop)
Cable
When using solid core cables, do not use the attached ring terminal. If you use the solid
core cables with the ring terminal, the ring terminal's pressure bonding may malfunction
and cause the cables to abnormally heat up.
B. For strand wiring
(1) Use ring terminals with insulating sleeves as shown in the fi gure below to connect to
the terminal block.
(2) Securely clamp the ring terminals to the cables using an appropriate tool so that the
cables do not come loose.
(3) Use the specifi ed cables, connect them securely, and fasten them so that there is no
Indoor unit
stress placed on the terminals.
(4) Use an appropriate screwdriver to tighten the terminal screws.
Do not use a screwdriver that is too small, otherwise, the screw heads may be dam-
aged and prevent the screws from being properly tightened.
*3
(5) Do not tighten the terminal screws too much, otherwise, the screws may break.
(6) See the table for the terminal screw tightening torques.
(7) Please do not fi x 2 power supply cables with 1 screw.
Strip 10 mm
Remote controller
Cable
Indoor unit
Use ring terminals and tighten the terminal screws to the specifi ed torques, otherwise,
abnormal overheating may be produced and possibly cause heavy damage inside the
unit.
M4 screw (Power supply/L, N, GND)
6.3.2. Transmission cable
Shielded cable (no fi lm)
• Connect transmission cables as shown in Fig. B.
• When the 2 cables are attached.
Fig. B
GOOD
Tighten the terminal screws to the specifi ed torques, otherwise, abnormal overheating
may be produced and possibly cause heavy damage inside the unit.
Loop
M3 screw (Transmission/X1, X2)
To peel the fi lm from the lead cable, use a dedicated tool that will not damage the
conductor cable.
When installing a screw on the terminal block, do not cut the cable by overtightening
the screw. On the other hand, an undertightened screw can cause faulty contact, which
will lead to a communication failure.
Remove it with the following sequence in case of the state with the grille.
WARNING
Screw with
special washer
Ring terminal
Terminal block
WARNING
Terminal number
30 mm
35 mm
PROHIBITED
Different diameter
WARNING
Terminal number
CAUTION
Ring terminal
Sleeve
Screw with
special washer
Ring terminal
Cable
Tightening torque
1.2 to 1.8 N·m (12 to 18 kgf·cm)
Connect to 1 side
Tightening torque
0.5 to 0.6 N·m (5 to 6 kgf·cm)