Ook voor Bosch FAP-OC 500Series: Handleiding voor installatie-instructies (21 pagina's), Gebruiksaanwijzing (40 pagina's), Installatiehandleiding (6 pagina's), Installatiehandleiding (28 pagina's), Gebruikershandleiding (48 pagina's), Gebruikershandleiding (48 pagina's), Installatiehandleiding (28 pagina's), Gebruiks- en onderhoudshandleiding (44 pagina's), Installatiehandleiding (32 pagina's), Gebruiks- en onderhoudshandleiding / Installatie-instructies (40 pagina's), Snelle referentiehandleiding (4 pagina's), Gebruiks- en onderhoudshandleiding (27 pagina's), Installatiehandleiding (24 pagina's), Installatiehandleiding (32 pagina's), Gebruiks- en onderhoudshandleiding (24 pagina's), Installatiehandleiding (28 pagina's), Servicehandleiding (41 pagina's), Gebruiks- en onderhoudshandleiding (21 pagina's), Installatiehandleiding (32 pagina's), Servicehandleiding (36 pagina's), Installatiehandleiding (32 pagina's), Snelstart- en veiligheidshandleiding (13 pagina's)

Bosch FAP-OC 500Series Productinformatie
Product Information 500 Series LSN Fire Detectors (EU)
7.3. Inspection Procedure for FAP−OC 500
1. Alternative
D On the central unit, switch the detector zone to be inspected into test mode. This
automatically sets the detector into revision operation and readies it for the detector
test.
. Only in revision operation the detector's individual sensors will trigger with the
corresponding test device. For an alarm, all sensors must trigger at the same time.
The C sensor is triggered using CO test aerosol, the O sensors by being covered
up. No O testing gas is required.
D Now hold the test device under the detector so that the test beaker is flush with the
trim ring and seals it tightly.
. Make sure that the test beaker does not tilt, which could cause the detector
to be lifted up and consequently become detached from its fastening.
D Spray the CO testing gas for approximately 1 sec.
. The test head must remain over the detector until the detector has been triggered.
Distribution of the CO−testing gas in the test head and therefore the sensor trigger
time can take up to 20 sec.
D Both scattered light areas are covered by the test beaker, so that both optical
sensors are also triggered at the same time.
D The detector triggers the alarm and the red alarm LED flashes.
Page 35
PI − 34.70 en
BDL−F.01U.025.876
A5.en/ 02.02.2006
ST−FIR/PRM1 / zab