2. 2.
Optional parts
The following options are available.
Description
Model
UTY-XWZXZ7
External con-
UTY-XWZXZ8
nect kit
UTY-XWZXZA
Extension
9708798011
cable
(service parts)
3.
ELECTRICAL REQUIREMENT
When connecting the Central remote controller, use the following wir-
ing.
Use
Size
Max.1.25 mm
(16AWG)
Power supply
cable
Min.0.5 mm
(20AWG)
2
Transmission
0.33mm
cable
(22AWG)
2
External input/
0.33mm
(22AWG)
output cable
Use
1Φ 50/60Hz 100-240V
Power supply
2 wire + earth (ground)
cable
(Always earth (ground) the unit)
L
W
Transmission
ON
ORKS
cable
compatible cable
External input/
Use cable in accordance with local rules for
output cable
cable
L
W
*
ON
ORKS
is registered trademark of Echelon Corporation in
the United States and other countries.
Fuse capacity
4.
SELECTING AN INSTALLATION LOCATION
4. 1.
Dimensions
(1)
Control unit
25.7(1)
162(6-3/8)
Front view
Side view
Application
For external input function
(Dry contact terminal / CN6
and CN7)
For external input function
(Apply voltage terminal / CN11
and CN12)
For external output function
(Output terminal / CN9)
Connect the power supply unit
and the control unit
(Cable length: 5m (16 ft.))
Cannot be replaced by any
other cable.
Wire type
2
Type60245 IEC57
or equivalent
2
22AWG LEVEL 4 (NEMA)
non-polar 2 core, twisted pair
solid core diameter 0.65mm
(1/32 in.)
2 core, twisted pair (Max.
cable length : 25m (82ft.)
Remark
5 A
Unit:
mm (in.)
118(4-21/32)
Rear view
(2)
Power supply unit
99 (3-29/32)
(1-13/16) (1-13/16)
46
46
2-Ø5
5
(3/16)
135 (5-5/16)
4. 2.
Installation restrictions
Make a service space to per-
form installation work.
5.
WIRING RULES
WARNING
Always use the accessories and specifi ed installation work parts.
Check the state of the installation parts. Not using the specifi ed
parts will cause fall, water leakage, electric shock, fi re, etc.
Install at a place that can withstand the weight of the unit and
install positively so that the unit will not topple or fall.
When installing this unit, make sure that there are no children
nearby. Otherwise, injury or electric shock could result.
After this unit is installed, perform a test run to verify that the
device operates normally. Then describe the operation method of
this unit to the customer.
Install a circuit breaker. Not installing a circuit breaker will cause
electric shock or fi re.
CAUTION
Before opening the case of this unit, remove all the static electric-
ity accumulated on the human body. It will cause an accident.
When the front cover fi xing screws are removed, be careful that
the front cover does not fall off. It will cause an injury.
The circuit boards of this unit are at both the front cover and rear
cover. When a cover is opened, the circuit boards may be dam-
aged by the screwdriver. This will cause an accident.
The front cover and rear cover are connected by wiring. When
disassembling, be sure that the wiring is not stretched.
Do not touch this unit's circuit board and circuit board parts directly
with your hands. Doing so may cause electric shock or injury.
Tightening the mounting screws too tight will damage the case of
this unit.
Unit: mm (in.)
29 (1-5/32)
(3/16)
39.2
(1-17/32)
Unit: mm (in.)
Service space
En-2