Atkinson Electronics GSCM-MINI Handmatig - Pagina 3

Blader online of download pdf Handmatig voor {categorie_naam} Atkinson Electronics GSCM-MINI. Atkinson Electronics GSCM-MINI 8 pagina's. Generator start control module
Ook voor Atkinson Electronics GSCM-MINI: Handmatig (16 pagina's)

Atkinson Electronics GSCM-MINI Handmatig
GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)
OPTION #1 MOMENTARY START CONTACT - TYPICAL GENERATOR W/ STARTER CONTROL BOX
The K1 relay is used to switch the start/crank input which is looking for a momentary signal and opens when the generator has
reached 50Hz, or half speed. The K2 relay provides a momentary "stop" signal until the generator AC Hz has dropped to zero.
For GSCM-mini operational sequence details see Page 4, Section - 1
OPTION #2 MAINTAINED START CONTACT TYPICAL GENERATOR W/ STARTER CONTROL BOX
The K1 relay provides a continuous run signal for
generators requiring a "maintained" start signal. The K2
relay provides a momentary "stop" signal until the generator
AC Hz has dropped to zero. For GSCM-mini operational
sequence details see Page 4, Section - 2
OPTION #3 IGNITION KEY SWITCH TYPE START CONTACT TYPICAL GENERATOR W/ STARTER CONTROL
The K1 relay is used to switch the starter input which is
looking for a momentary signal and opens when the
generator has reached 50Hz, or half speed. The K2 relay
provides a continuous run signal for generators requiring a
"maintained" ignition signal. When the GSCM-mini no
longer receives a run command signal (terminal 5 or
batteries fully charged, K2 relay opens telling the generator
to shutdown. For GSCM-mini operational sequence details
see Page 5, Section - 3
ATKINSON ELECTRONICS, INC.
Web Site: www.atkinsonelectronics.com
A double pole "kill switch" wired and installed by the user,
stops the generator instantly in emergency situations such as
a fuel spill. One switch pole (N.C.) kills power to the GSCM-
mini opening all relays. The other switch pole (N.O.) shorts
out the magneto for an instant stop.
A single pole "kill switch" wired and installed by the user,
stops the generator instantly in emergency situations such as
a fuel spill. One switch pole (N.C.) kills power to the GSCM-
mini opening all relays shutting down the ignition switch type
generators.
Distributed by:
GSCM-MINI
REV 9/05